ABB RELION REF615R Technical Manual page 597

Hide thumbs Also See for RELION REF615R:
Table of Contents

Advertisement

1MRS240050-IB C
12.2.1.2
12.2.1.3
REF615R
Technical Manual
User-programmable inverse-time characteristics
The user can define curves by entering parameters into the following standard formula:
A
t s
B k
[ ]
=
+
c
I
E
 −
I
>
A060641 V3 EN
t[s] Trip time (in seconds)
A
set
Curve parameter A
Curve parameter B
B
set
Curve parameter C
C
set
Curve parameter E
E
set
I
Measured current
Pickup value
I>
set
Time multiplier
k
set
RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is a ground-
fault specific characteristic.
The RI-type is calculated using the formula
k
t s
[ ]
=
I
>
0 339 0 236
.
.
 
×
I
A060642 V2 EN
The RD-type is calculated using the formula
I
t s
[ ]
5 8 1 35 In
.
.
=
×
k I
× >
A060643 V2 EN
General function block features
 
Section 12
(Equation 34)
(Equation 35)
(Equation 36)
591

Advertisement

Table of Contents
loading

Table of Contents