Section 3 Basic Functions; General Parameters - ABB RELION REF615R Technical Manual

Hide thumbs Also See for RELION REF615R:
Table of Contents

Advertisement

1MRS240050-IB C
Section 3
3.1
Table 4:
Analog input settings, phase currents
Parameter
Values (Range)
Secondary current
1=0.2A
2=1A
3=5A
Primary current
1.0...6000.0
Amplitude corr. A
0.900...1.100
Amplitude corr. B
0.900...1.100
Amplitude corr. C
0.900...1.100
Reverse polarity
0=False
1=True
Table 5:
Analog input settings, residual current
Parameter
Values (Range)
Secondary current
1=0.2A
2=1A
3=5A
Primary current
1.0...6000.0
Amplitude corr.
0.900...1.100
Reverse polarity
0=False
1=True
Table 6:
Analog input settings, phase voltages
Parameter
Values (Range)
Primary voltage
0.100...440.000
Secondary voltage
60...210
VT connection
1=Wye/Delta
2=Delta
3=VAB
4=VA
Amplitude corr. A
0.900...1.100
Table continues on next page
REF615R
Technical Manual
Basic functions

General parameters

Unit
Step
A
0.1
0.001
0.001
0.001
Unit
Step
A
0.1
0.001
Unit
Step
kV
0.001
V
1
0.001
Default
Description
2=1A
Rated secondary current
100.0
Rated primary current
1.000
Phase A amplitude correction factor
1.000
Phase B amplitude correction factor
1.000
Phase C amplitude correction factor
0=False
Reverse the polarity of the phase CTs
Default
Description
2=1A
Secondary current
100.0
Primary current
1.000
Amplitude correction
0=False
Reverse the polarity of the residual CT
Default
Description
20.000
Primary rated voltage
100
Secondary rated voltage
2=Delta
Wye or delta VT connection
1.000
Phase A Voltage phasor magnitude correction
of an external voltage transformer
Section 3
Basic functions
1)
41