Control Cabinet Pc And Display At Ups; Only Control Cabinet Pc Connected To Ups - Bosch Rexroth IndraControl VDP 16.3 Project Planning Manual

Operator display
Table of Contents

Advertisement

28/57
Dimensions, Installation and Wiring
5.3.3

Control cabinet PC and display at UPS

5.3.4

Only control cabinet PC connected to UPS

Bosch Rexroth AG R911323862_Edition 07
IndraControl VDP 16.3, VDP 40.3, VDP 60.3 Operator Dis‐
Overvoltage category I
(4)
16 A
24 V
A
24V IN
(4)
0V IN
0 V
A
6 mm ² (blue)
Functional earth
(1)
B
10 mm² (green/yellow)
6 mm² connect to functional earth of the operator display
6 mm ² connect to functional earth of the control cabinet PC
6 mm ² connect to functional earth of the UPS (VAU 01.1)
10 mm² (green/yellow)
Fig. 5-21:
PC (VSB 40.3, VSP xx.3, VPB 40.3, VPP xx.3) and display (VDP xx.
3) connected to an UPS
Overvoltage category I
(4)
16 A
24 V
A
24V IN
(4)
0 V
0V IN
A
6 mm ² (blue)
(1)
10 mm ² (green/yellow)
B
6 mm ²
a
connect to FE of the operator display.
6 mm ²
a
connect to FE of the control cabinet PC.
6 mm ²
a
connect to FE of the UPS (VAU 01.1).
10 mm² (green/yellow)
Fig. 5-22:
PC (VSB 40.3, VSP xx.3, VPB 40.3, VPP xx.3) connected to an
UPS. Display (VDP xx.3) not connected to an UPS
Terminal block UK6-FSI/6
with automatic cut-out TCP 10 A
(PHOENIX CONTACT) is recommended
UPS
(VAU 01.1)
24V OUT
X1S1
X1S2
0V OUT
Terminal block UK6-FSI/6
with automtatic cut-out TCP 4 A
(PHOENIX CONTACT)
(5)
Terminal block UK6-FSI/6
with automatic cut-out TCP 10 A
(PHOENIX CONTACT) is recommended
UPS
(VAU 01.1)
24V OUT
X1S1
X1S2
0V OUT
Terminal block UK6-FSI/6
with automatic cut-out TCP 4 A
(PHOENIX CONTACT)
FE
(5)
play
Control cabinet PC
VSB 40.3
VSP xx.3
VPB 40.3
VPB 40.4
VPP xx.3
(2)
+
(3)
X10
-
Functional earth
Operator display
(VDP xx.3)
+
(3)
X1S1
-
Functional earth
Control cabinet PC
VSB 40.3
VSP xx.3
VPB 40.3
VPP xx.3
(2)
+
(3)
X10
-
FE
Operator display
(VDP xx.3)
+
(3)
X1S1
-
FE