The EVO CS & CS-GEN2 commercial heat pump is the most efficient way to heat a commercial pool regardless of size or location. Our commercial heat pumps are ideal for sports and leisure centres, aquaculture, agriculture, water parks, hotels, resorts, apartments and office builds – there is no job in the field too big for the EVO CS Series! MODEL...
EvoHeat CS & CS-GEN2 Series Manual 3. Safety Instructions • Installation, repair or relocations must be done by a fully qualified person and not by the customer. If done incorrectly it may cause fire, electric shock, water leakage and other hazards.
EVOHEAT ACCESSORIES – DO NOT THROW AWAY All EvoHeat units are provided with rubber feet, controller and leads for the controller– do not throw them away as they are required as part of the installation.
When units of a similar height are placed side by side, EvoHeat recommend a 1500mm clearance between units. *Fan discharge distance can be reduced by adding a Plenum to alter the air flow direction. Contact EvoHeat or a HVAC specialist for further advice. If you do not have a location with these suggested clearances, please contact our EvoHeat Tech Support Specialist to discuss appropriate installation locations.
It is CRITICAL that there is sufficient water flow to the unit. Incorrect water flow can cause a loss of efficiency and possible damage to the unit. Optimal water flow rates are listed in the EvoHeat manual. It is imperative that water flow is kept as close as possible to these flow rates.
Correct phase connection is important with 3 phase heaters. NOTE: if 2 lights are showing on the 3 PHASE relay monitor this means the EvoHeat heat pump has been wired correctly (one orange light and one green light). If only one light is showing, the phases are out of rotation and need to be rotated to get the correct phase rotation.
EvoHeat CS & CS-GEN2 Series Manual 5. Operation 5.1 Main Controller Interface Button Name Function Press this button to start up/shut off the unit, cancel current operation or go back to ON/OFF previous interface. HELP Press this button to check button function of system state.
EvoHeat CS & CS-GEN2 Series Manual 5.2.3 Switching Modes At the main interface, you can switch between the modes of cooling, economic heating, heating & rapid heating by pressing . Example: Switch from Cooling mode to Economic Heating Note: The operation of mode is invalid if the unit you purchase is heating only or cooling only.
EvoHeat CS & CS-GEN2 Series Manual 5.2.7 Timer Settings Four timer periods can be set according to your needs. From the main interface, press to enter the timer setting, press DOWN to select Timer, then press to enter the timer setting interface. The process is much the same as adjusting the Clock settings. To cancel and return to the previous menu, press the ON/OFF button.
Page 13
EvoHeat CS & CS-GEN2 Series Manual 5.2.7.2 Daily Timer The Daily Timer allows you to apply your timers to particular days of the week. OFF means that the unit will not run on that day. • ON means the system will be running for a whole day.
EvoHeat CS & CS-GEN2 Series Manual 5.2.8 Keyboard Lock To lock the controller after adjusting settings, at the main interface hold the ON/OFF button for 5 seconds. The keyboard will be locked and display a lock symbol on the screen. To unlock the screen, hold the ON/OFF button for 5 seconds.
EvoHeat CS & CS-GEN2 Series Manual 6. Troubleshooting EvoHeat have developed a YouTube Channel where you will find useful videos regarding the CS Controller usage. www.youtube.com/evoheat IF YOUR HEAT PUMP ISN’T WORKING, CHECK THE FOLLOWING… • Is the screen of control panel lit? If not, make sure the electrical wires and cables are correctly connected and the power is on.
Page 16
If the water has no chlorine then it is condensation and is it normal – see drainage and condensation for more information. If the water has chlorine, it is a water leak and you need to contact EvoHeat tech support on 1300 859 933.
EvoHeat CS & CS-GEN2 Series Manual 6.1 Error Codes CODE FAILURE REASON SOLUTION Power on Normal working Inlet temp. sensor failure The temp sensor is broken or short circuit Check or change the temp. sensor Outlet temp. sensor failure The temp sensor is broken or short circuit Check or change the temp.
EvoHeat CS & CS-GEN2 Series Manual CODE FAILURE REASON SOLUTION Water-inlet and outlet temp. Water flow is not enough and low Check the pipe water flow and whether difference differential pressure the water system is jammed or not System 1/2/3/4 anti-freeze...
DO I NEED TO GET MY UNIT SERVICED? It is highly recommended that you get your EvoHeat unit serviced at least once a year by your local certified air conditioning or refrigeration technician. If your unit is located in a coastal area, more frequent maintenance may be necessary.
Warranty Registration EvoHeat highly recommend customers to complete their warranty details online to ensure efficient warranty claim processing. To register your warranty, scan our QR Code or head to our website and fill in the Warranty Registration Form: https://evoheat.com.au/warranty-registration/...