Problem
Normal mode (Charging)
• All LED display status are OFF.
• DC-UPS module does not operate.
Normal mode (Charging)
• Green LED display status is flashing
quickly.
• Red LED display status is On
(not flashing).
Normal mode (Charging)
• Orange LED display status is On
(not flashing).

Troubleshooting

Suggestion
1) Please check wiring and PSU output.
2) Replace DC-UPS module.
1) The input voltage is low (18-21 Vdc).
2) Re-check input voltage and increase to > 21 Vdc.
1) Check the Replace BAT relay contact. If it is "Close",
this either means:
- Battery connection is open or there is no battery
- Battery reverse polarity
- Battery spoil
2) Check battery polarity connection at
terminal and make corrections.
3) Check input polarity connection at
and make corrections.
4) Re-check battery voltage. If the battery still fails to
function and will not charge, replace with a new
battery (21-27.6 Vdc).
"BAT. IN"