Turn On PV Inverter

5.2.7.4 Grid Settings

Grid settings page includes the voltage and frequency protection points.
These protection points are linked to electricity regulations.
If there is no any special requirement, please do not change any grid settings.
Inverter ID: 002
Insulation
Country
Grid Settings
ENT
Voltage Protection
Freq. Protection
Reconnect T
P Ramp Up
6000%/m
EXIT
Voltage Protection
Freq. Protection
EXIT
Reconnect T
P Ramp Up
6000%/m
Figure 5-13 : Grid Settings page
ENT
High Off
High On
600s
High Off T
Low Off
EXIT
Low On
Low Off T
EXIT
Hi Off Slow
Hi On Slow
Hi Off Sl T
Lo Off Slow
EXIT
Lo On Slow
Lo Off Sl T
ENT
High Off
High On
600s
High Off T
Low Off
EXIT
Low On
Low Off T
EXIT
Hi Off Slow
Hi On Slow
Hi Off Slow T
Lo Off Slow
EXIT
Lo On Slow
Lo Off Slow T
42
276.0V
259.0V
0.3s
If user enters wrong settings
184.0V
Wrong Settings
219.0V
0.3s
Press ▲&▼ 5s
276.0V
259.0V
Do you want to set
U to the max range?
Yes / ►No
600.0s
184.0V
219.0V
1.0s
51.50Hz
50.05Hz
0.1s
If user enters wrong settings
47.50Hz
Wrong Settings
47.55Hz
0.1s
65.00Hz
Press ▲&▼ 5s
64.95Hz
Do you want to set
F to the max range?
Yes / ►No
5.0s
45.00Hz
45.55Hz
5.0s