ctrlX CORE
Connecting the reference conductor to the protective conductor
If the reference conductor 0 V (U
has to be arranged at a central place (e.g. at the load power supply unit). Hence, the supply current
circuit is a PELV circuit.

10.5.4 Grounding

NOTICE
Functional earth
Only the functional earth (FE) is used for the device. The functional earth is only used to dis-
charge disturbances. For individuals, the functional earth is not intended as protection against
electric shock.
The control is grounded via the top-hat rail. The top-hat rail, on which the control is mounted, has to be
mounted to a grounded metal carrier, e. g. the rear panel of the control cabinet.
The control is provided with FE springs (metal clips) at its bottom side creating an electric connection
to the mounting rail while mounting.
If necessary, provide the top-hat rail with a separate grounding connection.
Potential equalization
Potential equalization acc. to DIN VDE 0100 part 540 has to be provided between the system parts
and the voltage supply.

10.5.5 Shielding

NOTICE
The shielding reduces any effects of interferences on the system.
Observe the following when shielding:
Fasten the shielding as extensively as possible
Ensure proper contact between connector and terminal
Avoid damaging or squeezing conductors
Note the wire specifications when connecting the shielding
Shield the closest possible to the signal terminal points
Route all power cables and data cables in separate cable channels.
R911405645, Edition 02
) is connected to the protective conductor system, this connection
L
Failure due to insufficient grounding
An optimum grounding is required to impede possible interfer-
ences from the control and to discharge them to the ground.
Failure due to insufficient shielding
Provide sufficient shielding.