4.2MAX. Refrigerant pipe length and height difference
Model(Kbtu/h)
Max. refrigerant pipe
length
Max. difference in level
 
*Do your best to reduce the pipe length. Long pipe may cause capacity of the indoor unit incline. 
The refrigerant charge volume for the unit is based on using a 5m connecting pipe. If the connecting 
pipe's length is longer than 5m, it is advisable to charge additional Refrigerant for the unit in order to 
achieve better operation. 
Additional Refrigerant= (L-5)×0.035kg
(* "L" refers to length of connection pipe.)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
FLOOR STANDING AIR CONDITIONER TECHNICAL&SERVICE MANUAL V3.2
A
A
36K
15
m
7.5
m
 
 
42K,48K,60K
50
15
30