Specifications; Dimensions; Power Requirements; Environmental Operating Conditions - Thermo Scientific XBF40-MD Series Installation, Operation And Service Manual

Blast freezers
Table of Contents

Advertisement

1 Specifications

1.1 Dimensions

1.2 Power Requirements

1.3 Environmental
Operating Conditions
1.4 Refrigerant Types
and Charges
* Published interior volumes are nominal; usable capacities may be offset by shelves, carrying baskets, blower coils, or cabinet protrusions.
Thermo Scientific XBF40-MD Series Blast Freezers
*
Height
Interior: 51.23 in. (130.1 cm)
Exterior: 78 in. (196 cm)
Width
Interior: 34 in. (85 cm)
Exterior: 43.7 in. (111 cm)
Depth
Interior (Cabinet): 28.22 in. (71.1 cm)
Interior (Freeze Area): 14.5 in. (36.8 cm)
Exterior: 38.4 in. (96 cm)
Weight
754 lbs. (341 kg)
Voltage
208 / 230 V
Unit will not operate outside specified voltage range
Frequency
60 Hz only
Amperage
Minimum 20 A
NEMA receptacle required 6-20R
Dedicated circuit required for proper operation
Pollution Degree
Installation Category
Altitude
Humidity
Voltage Tolerance
Ambient Temperature
Product Usage
R-404a
41 oz. (1.162 Kg)
2
II
2000 m MSL (mean sea level)
max 60% in ambient up to 32 ° C (90°F)
±10%
15-32°C (59-90°F)
Indoor Use Only
Installation, Operation and Service Manual
Specifications
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xbf40d-md

Table of Contents