Firing Rates; Procedure To Refer Burner Operating Condition In High Altitude Plants - Riello RLS 70/EV Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burners
Table of Contents

Advertisement

3.8

Firing rates

MAXIMUM OUTPUT must be selected in area A (Fig. 4).
MINIMUM OUTPUT must not be lower than the minimum limit
shown in the diagram:
Model
RLS 70/EV
RLS 100/EV
3.8.1
Procedure to refer burner operating condition
in high altitude plants
Find the CORRECTED BURNER CAPACITY for the plant's alti-
tude in chart 1 and the CORRECTED PRESSURE in chart 2.
Check in the firing rate graph of the burner (Fig. 4), if the working
point defined by the values above is within the range limits.
If not, higher burner size is needed.
Note
 Charts are based only on altitude variation (reference temper-
ature = 68°F, 20°C)
 To get the combined correction in case of different air temper-
ature, a compensation of 1000 ft each 20°F (305 m each
11°C) is applicable (100 ft = 2°F).
Technical description of the burner
MBtu/hr
GPH
854
6.1
1330
9.5
RLS 70/EV
RLS 100/EV
NOTE:
The firing rate area given in Fig. 4 have been reduced by 10% with
respect to the maximum range that can be reached.
The firing rate area values have been obtained con-
sidering an ambient temperature of 68 °F, and an
atmospheric pressure of 394" WC and with the
combustion head adjusted.
WARNING
Example RLS 100/EV
Rated capacity = 3000 MBtu/hr - Rated air pressure = 1 "WC
Real altitude
= 3000 ft - Real temperature = 88 °F
= 88 °F - 68°F (reference temp.) = 20°F (equiva-
lent 1000 ft variation)
Proceeding as descripted above and considering a "virtual altitude"
of (3000 + 1000) ft:
the corrected capacity is 3425 MBtu/hr
the corrected burner air pressure is 1.14
11
GB
20066610