H-SERIES GREEN CLASS NET METER
6.0 METER INSTALLATION

6.1 Mounting the Green Class Net Meter

6-35/64
(166)
3-25/64
(86)
1-5/8
(41)
Use appropriately sized mounting hardware to fasten the meter enclosure to the
selected mounting surface.
The four housing mounting holes are centered 6.75" H x 4" W.
NOTE: Units housed in UL Type 1 JIC steel enclosures must only be installed in
indoor environments, where they will not be affected by the elements.

6.2 Main Power Board Connections

1. Installing a temporary ground for ESD protection: With all circuits de-energized,
connect a temporary protective earth ground connection for ESD protection.
Prior to performing any unit wiring, be sure to discharge any static on your per-
son.
2. * Installing the Green Class Net protective earth ground: Connect an earth
ground wire to the Green Class Net protective earth ground lug with a torque of
17 N-m. * for meters in metal enclosures.
62-0424-02
6-35/64 (166)
Ø 1-3/32 (28) THROUGH
3-17/64 (83)
NEAR SIDE ONLY
Fig. 5. Enclosure Dimensions
14
5/8 (16)
7-51/64
(198)
M34684