Honeywell H Series Installation Instructions Manual page 43

Green class net meter
Table of Contents

Advertisement

41043
2
41045
2
41047
2
41049
2
41051
2
41053
2
41055
2
41057
2
41059
2
41061
2
41063
2
41065
2
41067
2
41069
2
41071
2
41073
2
41075
2
41077
2
41079
2
41081
2
41083*** 2
41085*** 2
** To clear single meter kWh/kVARh, set multiple points at 41001 for 8 points with data set to
0000 0000 0000 0000 0000 0000 0000 0000. Jumper J6 m
*** External inputs are standard on Class Net Meters and optional on Class 3400 meters (Part of
Expanded Feature Package).To clear Auxiliary Inputs, set multiple points at 41083 or 41085 for
2 points with data set to 0000 0000. Jumper J6 must be closed.
BACnet
ID
Object
1
Analog Input Energy delivered
2
Analog Input Energy received
3
Analog Input Reactive energy delivered
Modbus Float Registers:
Apparent power, phase B
Apparent power, phase C
Power factor, phase A
Power factor, phase B
Power factor, phase C
Current, phase A
Current, phase B
Current, phase C
Voltage, line to neutral, phase A-N
Voltage, line to neutral, phase B-N
Voltage, line to neutral, phase C-N
Voltage, line to line, phase A-B
Voltage, line to line, phase B-C
Voltage, line to line, phase C-A
Phase angle, phase A
Phase angle, phase B
Phase angle, phase C
Reserved
Reserved
Reserved
External Input 1
External Input 2
BACnet Object Descriptors:
Description
H-SERIES GREEN CLASS NET METER
Units
kWh
kWh
kVARh Present Value R
43
kVA
R
kVA
R
% PF
R
% PF
R
% PF
R
Amps
R
Amps
R
Amps
R
Volts-N
R
Volts-N
R
Volts-N
R
Volts-L
R
Volts-L
R
Volts-L
R
Degree
R
Degree
R
Degree
R
Pulse
R/W
Pulse
R/W
Green
BACnet
Net
Property
Meters
Present Value R
Present Value R
62-0424-02

Advertisement

Table of Contents
loading