LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

Typical auxiliary output wiring

Two auxiliary open collector outputs and one auxiliary output connections are available on the panel, as detailed below:
Turns on during the panel's reset cycle. Can be used for resetting fire alarm system devices
Reset Output
such as roller-shutter doors or beam detectors. This output remains active for approximately
(RESET)
one second after all other outputs have returned to normal.
Turns on during any new fire alarm condition or when the panel's Silence/Resound Sounders
button is pressed to manually evacuate the building. The output turns off when the panel
is silenced. This output does not turn on when the Class Change or Alert inputs are asserted
Remote Output
(unless there are other fire alarm conditions present on the system). Note: It is possible to
(REM)
delay the activation of the Remote Output to correspond with any zone delay(s) that have
been programmed into the panel at access level 3. If required, the remote output can be
disabled by the user. When the Remote output is activated the Remote Output light will be
lit. This output will not operate from a non-latching zone.
This output provides a positive voltage supply for peripheral loads (such as relays) which are
controlled from the above outputs. It is protected by a current limiting fuse which trips if
Auxiliary 24V
one or more of the loads are shorted. This affects all loads and results in appropriate faults
Output
being reported at the panel. The current consumed by this output must be considered when
(AUX 24V)
calculating battery standby times. DO NOT CONNECT DOOR HOLDER CIRCUITS TO THIS
OUTPUT AS THEY WILL REDUCE BATTERY STANDBY TIME - USE A SEPARATE POWER SUPPLY.
Figure 7 : Typical auxiliary output wiring for open collector outputs
REM
RESET
AUX 24V
Two relay outputs are available on the panel, as detailed below:
Turns on during any fire alarm condition and off when the panel is reset. This output does
not turn on if the Class Change or Alert inputs are asserted or if the panel's Silence/Resound
Auxiliary Fire
Sounders button is pressed to manually evacuate the building (unless there are other fire
Output
alarm conditions present on the system). Note: It is possible to delay the activation of the
(AUX)
Auxiliary Output to correspond with any zone delay(s) that have been programmed into the
panel at access level 3. If required, the Auxiliary Output can be disabled by the user. This
output will not operate from a non-latching zone.
This output is normally energised. When a fault occurs, the output turns off to ensure failsafe
Fault Output
operation even in the event of total power loss. It is important that the peripheral part of the
(FAULT)
system this output drives is able to handle the output's 'normally on' condition. If required,
this output can be disabled by the user.
Connect each output to the relevant 5mm connector block on the Main Control PCB and terminate their screens
at the panel's base earth distribution post (see page 13 for more details).
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 9 of 24
+
+
RESET
REMOTE
RELAY
OUTPUT
RELAY
To protect the output stage, only
24V polarised relays with back EMF
diodes should be used. If any of
the relays are to be used to switch
Mains potentials, then suitable
relays
should
be
chosen
installed and wired accordingly, so
as not to compromise the electrical
safety of the fire alarm system.
and