Standby Battery Calculation Guide - C-TEC AlarmSense CFP702-2 Installation & Maintenance Manual

Lpcb approved cfp 2/4/8 zone fire alarm control panel
Table of Contents

Advertisement

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

STANDBY BATTERY CALCULATION GUIDE

The standby time of the fire alarm panel, after the Mains has failed, depends on the quiescent loading
of the panel, the alarm load of the panel, and the capacity of the batteries.
Note: LPCB approved systems must use 3.2Ah batteries (YUCEL Y3.2-12).
To determine the capacity of batteries required for any given standby period, the following formula
should be used:
Standby Time in Ah = 1.25 x [(TxA) + H x (P+Z)]
The multiplier 1.25 is present to account for lost capacity over the life of the batteries.
H = Number of hours standby required
P = The quiescent current of the panel = 0.025A
This figure is with the Mains failed, beeper operative and the Power Supply and General Fault lights lit.
If there are other quiescent drains on the panel then these must be included.
Z = The total quiescent current of all zone devices
See Zone Circuit specification on page 24 for quiescent consumption of AlarmSense™ devices.
A = The total alarm current of the sounders (plus any other devices connected to other alarm outputs).
See Zone Circuit specification on page 24 for quiescent consumption of AlarmSense™ devices. Also, take
into consideration conventional sounder load (where relevant).
T = The amount of time in hours required for the alarm (most commonly being half an hour).
Example 1:
The panel has 70 detectors each consuming 50µA each, 20 sounders at 20mA each, the required standby
time is 24 hours and the required alarm time is 0.5 hours.
Z = 70 x 0.00005 = 0.0035A
P = 0.025A
A = 20 x 0.02 = 0.4A
H = 24
T = 0.5
Standby Time in Ah = 1.25 x [(0.5 x 0.4) + 24 x (0.025 + 0.0035)] = 1.1Ah.
Therefore, batteries with at least 1.1Ah capacity are required.
Example 2:
The panel has 100 detectors each consuming 50µA each, 40 sounders at 20mA each, the required standby
time is 72 hours and the required alarm time is 0.5 hours.
Z = 100 x 0.00005 = 0.005A
P = 0.025A
A = 40 x 0.02 = 0.8A
H = 72
T = 0.5
Standby Time in Ah = 1.25 x [(0.5 x 0.8) + 72 x (0.025 + 0.005)] = 3.2Ah
Therefore, batteries with at least 3.2Ah capacity are required.
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 23 of 24

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alarmsense cfp704-2Alarmsense cfp708-2Cfp702-4Cfp704-4Cfp708-4Cfp 2 ... Show all

Table of Contents