C-TEC AlarmSense CFP702-2 Installation & Maintenance Manual page 17

Lpcb approved cfp 2/4/8 zone fire alarm control panel
Table of Contents

Advertisement

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
To program non-latching zones (
1.
Press the ACCESS LEVEL THREE FUNCTIONS button until the NONLATCHING light flashes (any zones that are already
programmed for non-latching operation will have their Zone Fault lights lit steady).
2.
To change the non-latching configuration press the NEXT OPTION button (Zone 1's Fault light will flash slower than the
NONLATCHING light if NOT programmed, or at the same rate if it is).
3.
If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4.
To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5.
Repeat steps 3 and 4 until the process is complete.
6.
To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
To program delays
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the DELAYS light flashes (any zones that are already programmed
for delays will have their Zone Fault lights lit steady, and similarly, if the Remote Output or Auxiliary Output are delayed,
then their relevant status lights will be lit steady. Note: Any existing fault indications will be temporarily suppressed during
this programming function. On exiting the function, the previous indications will be restored).
2. To change the delays configuration press the NEXT OPTION button (Zone 1's Fault light will flash slower than the DELAYS
light if NOT programmed, or at the same rate if it is).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5. Repeat steps 3 and 4 until the zone selection process is complete.
6. Pressing the NEXT OPTION button when on the last zone will select the Remote Output for editing. The output's current
status will be shown by the Remote Output Status light, in the same way as for the zones.
7. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
8. Pressing the NEXT OPTION button will select the Auxiliary Output for editing. The output's current status will be shown by
the Auxiliary Output Status light, in the same way as for the zones.
9. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
10. Pressing the NEXT OPTION button will return the selection to zone 1.
11. Set the delay period which will apply to all delayed zones or outputs by adjusting the VR1 control on the Main Control PCB
with a terminal screwdriver (this can be anything from 1 to 10 minutes), then press the ESCAPE ACCESS button or move
onto the next programming function by pressing the ACCESS LEVEL THREE FUNCTIONS button.
To program zones into test
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes (any zones that are already programmed for
test will have their Zone Fault lights lit steady).
2. To change the test configuration press the NEXT OPTION button (Zone 1's Fault light will flash slower than the TEST light if
NOT programmed, or at the same rate if it is).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5. Repeat steps 3 and 4 until the process is complete.
Important: Before testing any of the zones you have programmed for test, you must first press the ESCAPE ACCESS button.
Any zone(s) in test will be flashing and the General Test light will also be flashing. Testing can now commence. Remember
to take the relevant zones out of test when testing is complete.
To program the sounder status (new zone in alarm resounds, or does not resound, the sounders)
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the SOUNDER STATUS light flashes.
If the SOUNDER STATUS light flashes three times quickly with a longer off period, then an alarm in a new zone will
resound the sounders. If the SOUNDER STATUS light flashes with equal on-off periods, then an alarm in a new zone will
NOT resound the sounders.
2. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
3. To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
To program the sounder status (sounders fitted or not fitted)
1. Press the ACCESS LEVEL THREE FUNCTIONS button until the SOUNDER STATUS light flashes. Then press the ACCESS LEVEL
THREE FUNCTIONS button a second time.
Any zone circuits that are programmed (by default) to have sounders fitted will have their Zone Fault lights lit steady.
2. To change the configuration press the NEXT OPTION button (Zone 1's Fault light will flash at the same rate as the
SOUNDER STATUS light if sounders are programmed as fitted, or flash slower if programmed as NOT fitted).
3. If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4. To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5. Repeat steps 3 and 4 until the process is complete.
6. To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
The relevant part of the System Set-Up Data chart in the User Manual / Log Book must be updated if you
implement or make any changes to the coincidence, non-latching zones, delays, or sounder status functions.
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 17 of 24
Note: This function is non-compliant with EN54-2)