Accessing The Engineer Controls; Programming Coincidence, Non-Latching Zones, Delays, Test, Sounder Status - C-TEC AlarmSense CFP702-2 Installation & Maintenance Manual

Lpcb approved cfp 2/4/8 zone fire alarm control panel
Table of Contents

Advertisement

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

Accessing the engineer controls

Before programming the panel, please refer to pages 14 and 15 for an overview of the various engineering
functions available and the effect their implementation will have on the way the system operates.
To gain access to the panel's engineer functions, remove the panel lid using the Torx key provided and press the
ACCESS LEVEL THREE FUNCTIONS button on the Main Control PCB (see figure 12 below).
Figure 12 : Location of the panel's programming tools on the Main Control PCB
SW1
CODE ENTRY(1)
CODE ENTRY(2)
ESCAPE ACCESS
SW2
SW3
NEXT OPTION
CODE ENTRY(3)
SW4
ENABLE/DISABLE
LAMP TEST
CODE ENTRY(4)
CAUTION - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIES ACCORDING
TO THE MANUFACTURERS INSTRUCTIONS.
When the ACCESS LEVEL THREE FUNCTIONS button is pressed for
the first time, the Accessed light will be lit steady and the first
engineer function (COINCIDENCE) will be selected and indicated
by its yellow light flashing (see right).
Every time the ACCESS LEVEL THREE FUNCTIONS button is pressed
the next engineer function is selected.
Note: The engineer functions are graphically linked on the Main
Control PCB by an 'S' shaped line (see right). Pressing the ACCESS
LEVEL THREE FUNCTIONS button after the last selection (SOUNDER
STATUS) returns to the first function (COINCIDENCE).
To exit access level 3 at any time, press the ESCAPE ACCESS button.
Notes:
1. Access level 3 functions that are relevant to zones temporarily use the Zone Fault lights to show which zones
have been programmed for that function. This means any fault or disablement indication is suppressed until
the programming of the relevant function is complete.
2. When the panel's lid is removed, it is still possible to access the panel's authorised user control, i.e. access
level 2. This is done by entering the 2 1 4 3 entry code or, by turning the keyswitch to the 'I' position).
For detailed information on the authorised user controls, please refer to the separate User Manual / Log Book.
3. 'SYSTEM FAULT', 'REPEATER FAULT', 'HEAD OUT', 'OPEN CIRCUIT' and 'SHORT CIRCUIT' options are for fault
diagnosis purposes, as detailed on pages 18 to 22.
To program coincidence (Note: This function is non-compliant with EN54-2)
1.
Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes (any pairs of zones that are already
programmed for coincidence will have their Zone Fault lights lit steady).
2.
To change the coincidence configuration press the NEXT OPTION button (Fault lights for zones 1 and 2 will flash slower
than COINCIDENCE light if NOT programmed for coincidence, or at the same rate if they are).
3.
If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4.
Confirm your selection by pressing the NEXT OPTION button. This will move to the next pair of zones (if available).
5.
Repeat steps 3 and 4 until the process is complete.
6.
To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the
ACCESS LEVEL THREE FUNCTIONS button.
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 16 of 24
SW5
GENERAL
SILENCE
FIRE
INTERNAL
ZONE1
ZONE2
SOUNDER
SW6
SILENCE/
RESOUND
SOUNDERS
SW7
REMOTE
RESET
SUPPLY
OUTPUT
TEST
OK
I
SYSTEM
PSU
GENERAL
O
FAULT
FAULT
FAULT
5
4
6
ACCESS LEVEL 2
3
7
SW8
2
8
1
9
0
10
DELAY MINUTES
VR1
FIRE
ZONE3
ZONE4
ZONE5
ZONE6
ZONE7
FAULT
FAULT
GENERAL
OUTPUT
ACCESSED
DISABLEMENT
STATUS
REPEATER
HEAD
OPEN
SHORT
SOUNDER
CIRCUIT
CIRCUIT
FAULT
OUT
STATUS
OUTPUT
STATUS
COINCIDENCE
DELAYS TEST
ACCESS
NONLATCHING
LEVEL THREE
FUNCTIONS
ACCESS LEVEL THREE FUNCTIONS button
SYSTEM
FAULT
SENSITIVE TO STATIC
ELECTRICITY - OBSERVE
ZONE8
PRECAUTIONS BEFORE
HANDLING
WARNING
REMOVING THIS CIRCUIT
BOARD EXPOSES HAZARDOUS
VOLTAGES - PLEASE REFER TO
INSTALLATION INSTRUCTIONS
REMOTE
OUTPUT
STATUS
AUX
OUTPUTS
DELAYED
CFP ALARMSENSE PANEL CONTROLS
HEAD
REPEATER
OPEN
FAULT
OUT
CIRCUIT
SW8
COINCIDENCE
ACCESS
LEVEL THREE
NONLATCHING
FUNCTIONS
SHORT
SOUNDER
CIRCUIT
STATUS
DELAYS
TEST