Installing the standby battery supply
Two new, good quality and fully charged 12V 3.2A Hr valve regulated lead acid batteries are required
as the emergency stand-by power supply for the panel. The batteries should be connected in series
and located in the panel's enclosure as shown in Fig. 4 .
The battery leads, link wire and nylon cable ties are provided in the panel's accessory pack.
The panel's sophisticated battery monitoring unit protects the batteries against deep discharge by acti-
vating a cut off circuit when the stand-by supply voltage reaches 21V approx. If batteries are not fit-
ted, are discharged or in poor condition, a PSU fault will show at the panel.
Always dispose of used batteries according to the battery manufacturer's instructions.
Fig. 4 : Battery location and connection details
Fault relay output wiring
The repeater's failsafe fault relay output switches for any fault condition and is
capable of switching 1A @ 30Vdc. It must NOT be used for switching mains voltages.
Repeater network wiring
The repeater network should be wired in two-core 1.5mm
Fig. 5: Typical repeater network wiring
REPEATER 1
XFP
MAIN
NOT ALLOWED
=
At ONE panel only (repeater or
main), connect A to A,
B to B and terminate incoming
and outgoing earth screens to
the panel's side earth post.
This earth post must also be
connected to terminal C on the
network communication card's
connector block as shown.
IMPORTANT: At all other panels,
connect A to A, B to B and
terminate earth screens to
terminal C only.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200502 Rev 1 • Page 7 of 8
XFP 32 ZONE REPEATER PANEL
XFP
XFP
MASTER
REPEATER 2
REPEATER
REPEATER
SPUR WIRING
TO NEXT
REPEATER
PANEL IF
REQUIRED
Shorting link (supplied in panel accessory pack)
12V battery
Black wire from panel
Auxilliary
+24V I/P1 I/P2 0v
2
fire resistant screened cable.
XFP
REPEATER 5
REPEATER
SPUR WIRING
NOT ALLOWED
CAUTION - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIES ACCORDING
TO THE MANUFACTURERS INSTRUCTIONS.
NETWORK
COMMUNICATION
CARD
–
12V battery
Red wire from panel
Relay 1
Relay 2
Relay 3
NC
C
NO
NC
C
NO
NC
C
GENERAL
XFP
REPEATER 8
ZONE 2
FIRE
ZONE 1
REPEATER
ZONE 9
ZONE 10
D45
Mute
Beeper
SUPPLY
PRESENT
TEST
ACCESSED
GENERAL
PSU
SYSTEM
FAULT
FAULT
FAULT
WARNING
REMOVING THIS CIRCUIT
NETWORK
BOARD EXPOSES HAZARDOUS
VOLTAGES - PLEASE REFER TO
COMMUNICATION
INSTALLATION INSTRUCTIONS
TO NEXT
CARD
REPEATER
PANEL IF
REQUIRED
Fault
Sounder Circui
NO
NC
C
NO
+ 1 -
ZONE 4
ZONE 3
ZONE 5
ZONE 11
ZONE12
ZONE 13
GENERAL
DISABLEMENT
SOUNDER
STATUS
SENSITIVE TO STATIC
ELECTRICITY - OBSERVE
PRECAUTIONS BEFORE
HANDLING
+ 2
ZO
ZO
PH
EVAC
DE
RU