Specifications - Daikin FXMQ-MF Engineering Data

Outdoor air processing unit
Table of Contents

Advertisement

Specifications

2. Specifications
Model
1 Cooling Capacity
2 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin
Coil (Cross
Pitch
Fin Coil)
Face Area
Model
Type
Motor Output ×
Number of Units
Fan
Air Flow Rate (H/L)
External Static
Pressure 4
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Connections
Gas Pipes
Drain Pipe
Machine Weight (Mass)
Safety Devices
Refrigerant Control
Standard Accessories
Connectable Outdoor Units 5,6
Drawing No.
Notes:
 1 Nominal cooling capacities are based on the following conditions:
Outdoor temperature: 91°FDB, 82°FWB (68%RH)
Discharge set temp: 64°FDB
Equivalent ref. piping: 25ft (Horizontal)
 2 Nominal heating capacities are based on the following conditions:
Outdoor temperature: 32°FDB, 27°FWB (50%RH)
Discharge set temp: 77°FDB
Equivalent ref. piping: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
 4 Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its duct collection efficiency (gravity method) 50% or more.
 5 Within the range that the total capacity of indoor units is 50 to 100%, it is possible to connect to the outdoor unit.
 6 This equipment cannot be incorporated into the remote group control of the VRV III system.
4
FXMQ48MFVJU
Btu/h
48,000
Btu/h
30,000
Galvanized Steel Plate
in.
18'1/2''×29'1/4''×43'5/16''
in.
3×26×13
ft²
3.01
D13/4G2DA1
Sirocco Fan
W
380×1
cfm
635
in. WG
0.88
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber
4
3/8
in.
(Flare Connection)
5/8
in.
(Flare Connection)
PS1B (female thread)
Lbs
190
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual,
Sealing Pads, Screws, Clamps.
R-410A P series
C : 3D065463
FXMQ72MFVJU
72,000
47,000
Galvanized Steel Plate
18'1/2''×54'3/8''×43'5/16''
3×26×13
7.00
D13/4G2DA1
Sirocco Fan
380×1
988
0.96
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber
4
3/8
(Flare Connection)
3/4
(Brazing Connection)
PS1B (female thread)
271
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Screws, Clamps.
R-410A P series
C : 3D065463
EDUS39-900-F10
FXMQ96MFVJU
96,000
59,000
Galvanized Steel Plate
18'1/2''×54'3/8''×43'5/16''
3×26×13
7.00
D13/4G2DA1
Sirocco Fan
380×1
1,236
1.03
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Fiber
4
3/8
(Flare Connection)
7/8
(Brazing Connection)
PS1B (female thread)
271
Fuse
Thermal Protector
for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual,
Sealing Pads, Connection Pipes,
Screws, Clamps.
R-410A P series
C : 3D065463
FXMQ-MF

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fxmq48mfvjuFxmq72mfvjuFxmq96mfvju