Operation Limit

7. Operation Limit
FXMQ48MFVJU
Operation limit
(heating)
23
32
42.8
FXMQ72MFVJU
23
32
12
Fan only
operation
59
66.2
Outdoor air temp. (°F DB)
Fan only
operation
Operation limit
(heating)
59 66.2
Outdoor air temp. (°F DB)
89.6
Operation
limit
(cooling)
84.2
(92.3)
106.7 109.4
89.6
Operation
limit
(cooling)
86
(92.3)
106.7 109.4
EDUS39-900-F10
NOTE
1) These figures assume the
following operating conditions.
(Indoor and outdoor units)
Equivalent pipe length: 25ft.
Level difference: 0ft.
2)
:The discharge air temperature
may not match the temperature
setting for too large outdoor-air
processing capacity.
Thermostat OFF may be carried out.
3)
: The discharge air temperature
may not match the temperature
setting for too small outdoor-air
processing capacity.
4) The system will not operate in fan
mode when the outdoor-air
temperature is 41°F or below.
C : 3D046312
NOTE
1) These figures assume the
following operating conditions.
(Indoor and outdoor units)
Equivalent pipe length: 25ft.
Level difference: 0ft.
2)
:The discharge air temperature
may not match the temperature
setting for too large outdoor-air
processing capacity.
Thermostat OFF may be carried out.
3)
: The discharge air temperature
may not match the temperature
setting for too small outdoor-air
processing capacity.
4) The system will not operate in fan
mode when the outdoor-air
temperature is 41°F or below.
C : 3D047750