Alpha ESS SMILE-S6-HV Installation Manual page 65

Energy storage system (ess)
Hide thumbs Also See for SMILE-S6-HV:
Table of Contents

Advertisement

zz
100022
MPPT2_SW_OCP
100023
MPPT2_HW_OCP
100024
MPPT2_OTP
100025
BAT_OVP
100026
BAT_UVP
100027
Battery_lose
100028
BAT_OTP
100029
BAT1_charge_OCP
100030
BAT1_discharge_OCP
100031
BAT2_charge_OCP
100032
BAT2_discharge_OCP
100033
BAT1_HW_OCP
100034
BAT2_HW_OCP
100035
INV_OTP
100036
INV_OVP
100037
INV_UVP
Output_DC_
100038
over_current
100039
INV_OCP
100040
INV_HW_OCP
Output_DC_
100041
over_voltage
___________________________________________________________________
1. Try to reduce the PV power.
2. Restart the inverter to see if the fault still exists. If it still
exists, contact service.
1. Try to lower the ambient temperature.
2. Make sure that the inverter is installed according to the
manual and there is no shelter around the inverter.
3. After the inverter is powered off and waiting for 30
minutes, then restart it. If the fault still exists, contact ser-
vice.
Check whether the actual battery voltage exceeds the bat-
tery charging cut-off voltage by more than 20V.
Check whether the actual battery voltage is lower than the
battery discharge cut-off voltage.
Confirm that the wiring is normal, and check whether the
battery voltage sampling value is less than 75V.
1. Try to lower the ambient temperature.
2. Make sure that the inverter is installed according to the
manual and there is no shelter around the inverter.
3. After the inverter is powered off and waiting for 30
minutes, then restart it. If the fault still exists, contact ser-
vice.
1. Try to reduce battery power.
2. Restart the inverter to see if the fault still exists. If it still
exists, contact service.
1. Try to lower the ambient temperature.
2. Make sure that the inverter is installed according to the
manual and there is no shelter around the inverter.
3. After the inverter is powered off and waiting for 30
minutes, then restart it. If the fault still exists, contact ser-
vice.
The effective value of grid voltage exceeds the maximum
protection value of national standard voltage.
1. Whether the off grid output terminal is short circuited or
has impact load.
2. Restart the inverter to see if the fault still exists. If it still
exists, contact service.
Restart the inverter to see if the fault still exists. If it still ex-
ists, contact service.
1. Check whether the off grid output terminal is overloaded,
short circuited or has impact load.
2. Restart the inverter to see if the fault still exists. If it still
exists, contact service.
Restart the inverter to see if the fault still exists. If it still ex-
ists, contact service.