Catalog SIMATIC NET Networking Components RUGGEDCOM Modules For RX1500, RX1501, RX1510, RX1511, RX1512, RX1524, RX1536 Edition 07/2021 https://www.siemens.com...
Page 2
Preface Introduction Power Supply Modules SIMATIC NET Copper Ethernet Modules Networking Components Fiber Optic Ethernet RUGGEDCOM Modules Modules WAN Modules Catalog Cellular Modem Modules RUGGEDCOM APE Modules Blank Modules For RX1500, RX1501, RX1510, RX1511, RX1512, RX1524, RX1536 07/2021 C79000-G8976-1320-16...
Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Accessing Documentation ...................... vii Registered Trademarks ......................vii Warranty ..........................viii Training ..........................viii Customer Support ......................... viii Contacting Siemens ........................ ix Ordering RUGGEDCOM Products ..................... ix Introduction ........................... 1 Available Modules ....................2 Supported Modules by Device ................15 Installing/Removing Modules ................
Siemens Customer Support. Registered Trademarks RUGGEDCOM®, ROS®, RCDP®, and RUGGEDCOM Discovery Protocol® are registered trademarks of Siemens Canada Ltd. Linux® is the registered trademark of Linus Torvalds in the United States and other countries. The registered trademark Linux® is used pursuant to a sublicense from LMI, the exclusive licensee of Linus Torvalds, owner of the mark on a world-wide basis.
Siemens Sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, contact Siemens Customer Support through any of the following methods: Online Visit http://www.siemens.com/automation/support-request...
E-Mail info.ruggedcom@siemens.com https://www.siemens.com Ordering RUGGEDCOM Products Use the RUGGEDCOM -Selector to select and configure RUGGEDCOM products and accessories. Once selected, an item(s) can be transferred to the Siemens Industry Mall and ordered. RUGGEDCOM-Selector http://www.siemens.com/ruggedcom-selector. For more information, refer to https://www.siemens.com.
Introduction This catalog details the various power and line modules available for the RUGGEDCOM RX1500/RX1501/RX1510/RX1511/RX1512/RX1524/RX1536. Modules allow network designers to quickly and cost effectively adjust their communications infrastructure to the needs of the facilities and the network. It is intended to be used as a supplement to the Installation Manual for the device. For a list of related Installation Manuals, refer to "Related Documents (Page vii)".
Introduction 1.1 Available Modules Available Modules The following is a list of all power and line modules available for use in the RUGGEDCOM RX1500/RX1501/RX1510/RX1511/RX1512/RX1524/RX1536. Power Supply Modules Note The RUGGEDCOM RX1512 features a built-in power supply. RUGGEDCOM RX1500PN PS 12 (shipped until Specifications Article Numbers 2019)
Page 20
Introduction 1.1 Available Modules Antennas: 1 x EVDO Rev A, 1 x Receive Diversity (Secondary) SIM: Dual Mini-SIM (2FF) RUGGEDCOM RX1500PN LM W22 Specifications Article Numbers Services: EVDO Rev A 6GK6015-0AL20-0WE0 (Standard) Region: North America (Verizon) 6GK6015-0AL20-0WE1 (Conformal Coated) Port Type: 50 Ω SMA Antennas: 2 x EVDO Rev A, 2 x Receive Diversity (Secondary)
Page 21
Introduction 1.1 Available Modules SIM: Dual Mini-SIM (2FF) RUGGEDCOM RX1500PN LM W61 Specifications Article Numbers Services: 4G LTE/HSPA+/ 6GK6015-0AL20-0WJ0 CDMA/EVDO/GPS/GNSS (Standard) Region: North America 6GK6015-0AL20-0WJ1 (Verizon, Sprint) (Conformal Coated) Port Type: 50 Ω SMA Antennas: 1 x LTE Main, 1 x LTE MIMO, 1 x GPS SIM: Dual Mini-SIM (2FF) RUGGEDCOM RX1500PN LM W81...
Page 24
Introduction 1.1 Available Modules Processor: Intel x5- 6GK6015-0AL20-0GJ1 E3940 1.8 GHz, 2 MB L2 (Conformal Coated) Cache RAM: 8 GB DDR3 ECC, 1600 MHz, 32-bit Disk: 64 GB, Solid State Networking: Intel I210, RJ45 Gigabit Ethernet Interface USB: 2 x USB 3.0 Video: Intel HD Graphics Processor, Display Port RUGGEDCOM RX1500PN LM APE1808ADM...
Page 25
Introduction 1.1 Available Modules RAM: 8 GB DDR3 ECC, 1600 MHz, 32-bit Disk: 64 GB, Solid State Networking: Intel I210, RJ45 Gigabit Ethernet Interface USB: 2 x USB 3.0 Video: Intel HD Graphics Processor, Display Port Maximum combined USB device power consumption is 500 mA at 5 V. Blank Modules RUGGEDCOM RX1500PN PS XXP Specifications...
Introduction 1.2 Supported Modules by Device Supported Modules by Device Most devices in the RUGGEDCOM RX1500 product family support most, if not all available modules. Restrictions exist for some. Before selecting/installing a module, verify first if it is supported by the target device. Power Supply Modules Module RUGGEDCOM RX1500PN PS 12...
Introduction 1.3 Installing/Removing Modules Installing/Removing Modules Always refer to the Installation Manual for the host device RUGGEDCOM RX1500 for instructions on how to install or remove a power or line module. The Installation Manual cites important, chassis-specific safety warnings that should be followed to avoid damage to the module and/or device.
Introduction 1.4 Dimensions Dimensions Power and line modules conform to the following dimensions: Note All dimensions are in millimeters (mm). Power Supply Module Dimensions 162.5 151.8 40.6 Figure 1.1 Power Supply Module Dimensions Line Module Dimensions 162.5 151.4 19.7 Figure 1.2 Line Module Dimensions RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Power Supply Modules The following power supply modules are available for the RUGGEDCOM RX1500 series devices, excluding the RUGGEDCOM RX1512. Note The RUGGEDCOM RX1512 features a built-in power supply. RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Power Supply Modules 2.1 RUGGEDCOM RX1500PN PS 12 RUGGEDCOM RX1500PN PS 12 The RUGGEDCOM RX1500PN PS 12 power supply module provides 12 VDC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a removable screw terminal block and a failsafe relay terminal block.
Page 34
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Power Supply Modules 2.2 RUGGEDCOM RX1500PN PS 12P RUGGEDCOM RX1500PN PS 12P The RUGGEDCOM RX1500PN PS 12P power supply module provides 12 VDC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a 3-position European-style (Euroblock) terminal block and a failsafe relay terminal block.
Page 36
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Power Supply Modules 2.3 RUGGEDCOM RX1500PN PS 24 RUGGEDCOM RX1500PN PS 24 The RUGGEDCOM RX1500PN PS 24 power supply module provides 24 VDC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a removable screw terminal block and a failsafe relay terminal block.
Page 38
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Power Supply Modules 2.4 RUGGEDCOM RX1500PN PS 24P RUGGEDCOM RX1500PN PS 24P The RUGGEDCOM RX1500PN PS 24P power supply module provides 24 VDC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a 3-position European-style (Euroblock) terminal block and a failsafe relay terminal block.
Page 40
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Power Supply Modules 2.5 RUGGEDCOM RX1500PN PS 48 RUGGEDCOM RX1500PN PS 48 The RUGGEDCOM RX1500PN PS 48 power supply module provides 48 VDC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a removable screw terminal block and a failsafe relay terminal block.
Page 42
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Power Supply Modules 2.6 RUGGEDCOM RX1500PN PS 48P RUGGEDCOM RX1500PN PS 48P The RUGGEDCOM RX1500PN PS 48P power supply module provides 48 VDC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a 3-position European-style (Euroblock) terminal block and a failsafe relay terminal block.
Page 44
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Power Supply Modules 2.7 RUGGEDCOM RX1500PN PS HI RUGGEDCOM RX1500PN PS HI The RUGGEDCOM RX1500PN PS HI power supply module provides high VDC or VAC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a removable screw terminal block and a failsafe relay terminal block.
Page 46
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Power Supply Modules 2.8 RUGGEDCOM RX1500PN PS HIP RUGGEDCOM RX1500PN PS HIP The RUGGEDCOM RX1500PN PS HIP power supply module provides high VDC or VAC power to the host device and features a failsafe relay to protect against critical error conditions. It is equipped with a 3-position European-style (Euroblock) terminal block and a failsafe relay terminal block.
Page 48
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Page 49
Power Supply Modules 2.8 RUGGEDCOM RX1500PN PS HIP RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Copper Ethernet Modules The following copper Ethernet modules are available for the RUGGEDCOM RX1500 series devices. RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Copper Ethernet Modules 3.1 RUGGEDCOM RX1500PN LM CG01 RUGGEDCOM RX1500PN LM CG01 The RUGGEDCOM RX1500PN LM CG01 module features two 10/100/1000Base-TX copper RJ45 Ethernet ports. Description Ethernet Ports Port LEDs Figure 3.1 RUGGEDCOM RX1500PN LM CG01 Ethernet Ports Fixed 10/100/1000Base-TX copper RJ45 Ethernet ports. Port LEDs Each port features a dedicated LED that indicates its link/activity state.
Page 52
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Page 53
Copper Ethernet Modules 3.1 RUGGEDCOM RX1500PN LM CG01 Certification Details A copy of the Material Declaration is available online at https:// support.industry.siemens.com/cs/ww/en/view/109738831. Ordering Information Description 2 x 10/100/1000TX RJ45 Article Numbers 6GK6015-0AL20-0FC0 (Standard) 6GK6015-0AL20-0FC1 (Conformal Coated) RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Copper Ethernet Modules 3.2 RUGGEDCOM RX1500PN M12 CG03 RUGGEDCOM RX1500PN M12 CG03 The RUGGEDCOM RX1500PN M12 CG03 module features two 10/100/1000Base-TX copper M12 (8-pin, A-coded) Ethernet ports. Description M12 Port Port LED Figure 3.3 RUGGEDCOM RX1500PN M12 CG03 Ethernet Ports Fixed 10/100/1000Base-TX copper M12 Ethernet ports. Port LEDs Each port features a dedicated LED that indicates its link/activity state.
Page 55
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Copper Ethernet Modules 3.3 RUGGEDCOM RX1500PN M12 CG03B RUGGEDCOM RX1500PN M12 CG03B The RUGGEDCOM RX1500PN M12 CG03B module features two 10/100/1000Base- TX copper M12 (8-pin, A-coded) Ethernet ports. Both ports can be utilized as bypass ports to protect the network from power disruptions. Description M12 Port Port LED...
Page 58
Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: China RoHS 2 •...
Copper Ethernet Modules 3.4 RUGGEDCOM RX1500PN M12 X CG04 RUGGEDCOM RX1500PN M12 X CG04 The RUGGEDCOM RX1500PN M12 X CG04 module features two 10/100/1000Base-TX copper M12 (8-pin, X-coded) Ethernet ports. Description M12 Port Port LED Figure 3.7 RUGGEDCOM RX1500PN M12 X CG04 Ethernet Ports Fixed 10/100/1000Base-TX copper M12 Ethernet ports.
Page 61
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Copper Ethernet Modules 3.5 RUGGEDCOM RX1500PN M12 X CG04B RUGGEDCOM RX1500PN M12 X CG04B The RUGGEDCOM RX1500PN M12 X CG04B module features two 10/100/1000Base- TX copper M12 (8-pin, X-coded) Ethernet ports. Both ports can be utilized as bypass ports to protect the network from power disruptions. Description M12 Port Port LED...
Page 64
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Copper Ethernet Modules 3.6 RUGGEDCOM RX1500PN M12 4TX03 RUGGEDCOM RX1500PN M12 4TX03 The RUGGEDCOM RX1500PN M12 4TX03 module features four 10/100Base-TX copper M12 (8-pin, A-Coded) Ethernet ports. Description M12 Port Port LED Figure 3.11 RUGGEDCOM RX1500PN M12 4TX03 Ethernet Ports Fixed 10/100Base-TX copper M12 Ethernet ports. Port LEDs Each port features a dedicated LED that indicates its link/activity state.
Page 67
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Copper Ethernet Modules 3.7 RUGGEDCOM RX1500PN M12 4TX03B RUGGEDCOM RX1500PN M12 4TX03B The RUGGEDCOM RX1500PN M12 4TX03B module features four 10/100Base-TX copper M12 (8-pin, A-coded) Ethernet ports. Two of the available ports can be utilized as bypass ports to protect the network from power disruptions. Description M12 Port M12 Port with Controlled Bypass...
Page 70
Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: China RoHS 2 •...
Copper Ethernet Modules 3.8 RUGGEDCOM RX1500PN M12 4TX04 RUGGEDCOM RX1500PN M12 4TX04 The RUGGEDCOM RX1500PN M12 4TX04 module features four 10/100Base-TX copper M12 (4-pin, D-coded) Ethernet ports. Description M12 Port Port LED Figure 3.15 RUGGEDCOM RX1500PN M12 4TX04 Ethernet Ports Fixed 10/100Base-TX copper M12 Ethernet ports. Port LEDs Each port features a dedicated LED that indicates its link/activity state.
Page 73
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Copper Ethernet Modules 3.9 RUGGEDCOM RX1500PN M12 4TX04B RUGGEDCOM RX1500PN M12 4TX04B The RUGGEDCOM RX1500PN M12 4TX04B module features four 10/100Base-TX copper M12 (4-pin, D-coded) Ethernet ports. Two of the available ports can be utilized as bypass ports to protect the network from power disruptions. Description M12 Port M12 Port with Controlled Bypass...
Page 75
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Copper Ethernet Modules 3.10 RUGGEDCOM RX1500PN LM 6TX01 3.10 RUGGEDCOM RX1500PN LM 6TX01 The RUGGEDCOM RX1500PN LM 6TX01 module features six 10/100Base-TX copper RJ45 Ethernet ports. Description Ethernet Ports Port LEDs Figure 3.19 RUGGEDCOM RX1500PN LM 6TX01 Ethernet Ports Fixed 10/100Base-TX copper RJ45 Ethernet ports. Port LEDs Each port features a dedicated LED that indicates its link/activity state.
Page 77
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Page 78
Copper Ethernet Modules 3.10 RUGGEDCOM RX1500PN LM 6TX01 Certification Details A copy of the Material Declaration is available online at https:// support.industry.siemens.com/cs/ww/en/view/109738831. Ordering Information Description 6 x 10/100TX RJ45 Article Numbers 6GK6015-0AL20-0NB0 (Standard) 6GK6015-0AL20-0NB1 (Conformal Coated) RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Fiber Optic Ethernet Modules The following fiber optic Ethernet modules are available for the RUGGEDCOM RX1500 series devices. RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Fiber Optic Ethernet Modules 4.1 RUGGEDCOM RX1500PN LM 4FX11 RUGGEDCOM RX1500PN LM 4FX11 The RUGGEDCOM RX1500PN LM 4FX11 module features four 10/100Base-FX fiber optic Ethernet ports. Note When connecting cables, make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link. Description Ethernet Ports Port LEDs...
Page 82
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Fiber Optic Ethernet Modules 4.2 RUGGEDCOM RX1500PN LM FL01 RUGGEDCOM RX1500PN LM FL01 The RUGGEDCOM RX1500PN LM FL01 module features three 10Base-FL/100Base-SX fiber optic Ethernet ports. Note When connecting cables, make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link. Description Ethernet Ports Port LEDs...
Page 84
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Fiber Optic Ethernet Modules 4.3 RUGGEDCOM RX1500PN LM FG03 RUGGEDCOM RX1500PN LM FG03 The RUGGEDCOM RX1500PN LM FG03 module features two 1000Base-LX fiber optic Ethernet ports. Note When connecting cables, make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link. Description Ethernet Ports Port LEDs...
Page 86
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM SFP Transceiver Catalog [https:// support.industry.siemens.com/cs/ca/en/view/109482309]. Port LEDs Each transceiver socket features a dedicated LED that indicates the link/ activity state of the associated SFP transceiver.
Page 88
4.4 RUGGEDCOM RX1500PN LM FG50 Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Fiber Optic Ethernet Modules 4.5 RUGGEDCOM RX1500PN LM FG51 RUGGEDCOM RX1500PN LM FG51 The RUGGEDCOM RX1500PN LM FG51 module features two 10/100/1000Base-SX fiber optic Ethernet ports. Note When connecting cables, make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link. Description Ethernet Ports Port LED...
Page 90
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM SFP Transceiver Catalog [https:// support.industry.siemens.com/cs/ca/en/view/109482309]. Port LEDs Each transceiver socket features a dedicated LED that indicates the link/ activity state of the associated SFP transceiver.
Page 92
4.6 RUGGEDCOM RX1500PN LM FX50 Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Fiber Optic Ethernet Modules 4.7 RUGGEDCOM RX1500PN LM FX51 RUGGEDCOM RX1500PN LM FX51 The RUGGEDCOM RX1500PN LM FX51 module features two 10/100Base-FX fiber optic Ethernet ports. Note When connecting cables, make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link. Description Ethernet Ports Port LEDs...
Page 94
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM SFP Transceiver Catalog [https:// support.industry.siemens.com/cs/ca/en/view/109482309]. Port LEDs Each transceiver socket features a dedicated LED that indicates the link/ activity state of the associated SFP transceiver.
Page 96
4.8 RUGGEDCOM RX1500PN LM 6FX50 Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Fiber Optic Ethernet Modules 4.9 RUGGEDCOM RX1500PN LM 6FX51 RUGGEDCOM RX1500PN LM 6FX51 The RUGGEDCOM RX1500PN LM 6FX51 module features six 10/100Base-FX fiber optic Ethernet ports. Note When connecting cables, make sure the Transmit (Tx) and Receive (Rx) connections of each port are properly connected and matched to establish a proper link. Description Ethernet Ports Port LED...
Page 98
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
WAN Modules The following Wireless Area Network (WAN) modules are available for the RUGGEDCOM RX1500 series devices. RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
WAN Modules 5.1 RUGGEDCOM RX1500PN LM S01 RUGGEDCOM RX1500PN LM S01 The RUGGEDCOM RX1500PN LM S01 module features six serial RJ45 ports that may be used with a null modem (crossover) serial cable. Description Serial Ports Port LED Figure 5.1 RUGGEDCOM RX1500PN LM S01 Serial Ports Serial RJ45 ports.
Page 102
WAN Modules 5.1 RUGGEDCOM RX1500PN LM S01 Pin-Out Description The following are the pin-out descriptions for the RJ45 ports: Figure 5.2 Serial RJ45 Port RS232 Mode RS485 Mode RS422 Mode RX- (Receive Negative) Reserved (Do Not Connect) Common (Isolated) Ground RX (Receive) ...
Page 103
WAN Modules 5.1 RUGGEDCOM RX1500PN LM S01 The following illustration demonstrates the recommended RS485 wiring scheme: 120Ω 10nF 120Ω 10nF RUGGEDCOM RX1500PN LM S01 Module and Host Device Common (Isolated Ground) Negative Positive Shield to Earth (Connected At a Single Point) RS485 Devices (32 Total) Figure 5.3 Recommended RS485 Wiring...
Page 104
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
WAN Modules 5.2 RUGGEDCOM RX1500PN LM TC1 RUGGEDCOM RX1500PN LM TC1 The RUGGEDCOM RX1500PN LM TC1 module features a single T1/E1 RJ48C port for connection to a Wide Area Network (WAN). Requirements/Restrictions Chassis Only one T1/E1 module is permitted per device. Description WAN Port TX LED...
Page 106
WAN Modules 5.2 RUGGEDCOM RX1500PN LM TC1 Installing the Module For information about installing this module, refer to the Installation Manual for the host device. Pin-Out Description The following is the pin-out for the RJ48C port: Figure 5.5 RJ48C Pin Configuration Name Description RRING Receive Negative...
Page 107
5.2 RUGGEDCOM RX1500PN LM TC1 Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
WAN Modules 5.3 RUGGEDCOM RX1500PN LM TC2 RUGGEDCOM RX1500PN LM TC2 The RUGGEDCOM RX1500PN LM TC2 module features two T1/E1 RJ48C ports for connection to a Wide Area Network (WAN). Requirements/Restrictions Chassis Only one T1/E1 module is permitted per device. Description WAN Ports TX LED RX LED...
Page 109
WAN Modules 5.3 RUGGEDCOM RX1500PN LM TC2 Installing the Module For information about installing this module, refer to the Installation Manual for the host device. Pin-Out Description The following is the pin-out for the RJ48C ports: Figure 5.7 RJ48C Pin Configuration Name Description RRING Receive Negative...
Page 110
5.3 RUGGEDCOM RX1500PN LM TC2 Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
WAN Modules 5.4 RUGGEDCOM RX1500PN LM TC4 RUGGEDCOM RX1500PN LM TC4 The RUGGEDCOM RX1500PN LM TC4 module features four T1/E1 RJ48C ports for connection to a Wide Area Network (WAN). Requirements/Restrictions Chassis Only one T1/E1 module is permitted per device. Description WAN Ports TX LED RX LED...
Page 112
WAN Modules 5.4 RUGGEDCOM RX1500PN LM TC4 Installing the Module For information about installing this module, refer to the Installation Manual for the host device. Pin-Out Description The following is the pin-out for the RJ48C ports: Figure 5.9 RJ48C Pin Configuration Name Description RRING Receive Negative...
Page 113
5.4 RUGGEDCOM RX1500PN LM TC4 Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
WAN Modules 5.5 RUGGEDCOM RX1500PN LM E02 RUGGEDCOM RX1500PN LM E02 The RUGGEDCOM RX1500PN LM E02 module features two sets of E1 BNC ports for connection to a Wide Area Network (WAN). Description E1 BNC Ports Port LEDs Figure 5.10 RUGGEDCOM RX1500PN LM E02 WAN Ports Fixed E1 BNC ports.
Page 115
Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: China RoHS 2 •...
WAN Modules 5.6 RUGGEDCOM RX1500PN LM D02 RUGGEDCOM RX1500PN LM D02 The RUGGEDCOM RX1500PN LM D02 module features a single Digital Data Services (DDS) port that supports line rates of 56 kbps (Master/Slave) and 64 kbps (Slave). Note This module is not RoHS certified. It must be purchased separately from any RUGGEDCOM RX1500 series device.
Page 117
WAN Modules 5.6 RUGGEDCOM RX1500PN LM D02 Standards and Operating Modes The module is compatible with the following standards: • AT&T PUB 62310 (Standard DDS) • BELLCORE TA-TSY-000077 • BELLCORE TR-TSY-000458 • ANSI T1.410 It also supports the following operating modes, which are configurable via the operating system for the host device: Operating Mode Line Rate...
Page 118
WAN Modules 5.6 RUGGEDCOM RX1500PN LM D02 Connector RJ48 Environment Operating Temperature -40 to 85 °C (-40 to 185 °F) Operating Relative Humidity 5 to 95% (non-condensing) Storage Temperature -40 to 85 °C (-40 to 185 °F) Ordering Information Description 1k DDS RJ48 (56k Master/Slave, 64 Slave) Article Numbers 6GK6015-0AL20-0LB0 (Standard) 6GK6015-0AL20-0LB1 (Conformal Coated)
Cellular Modem Modules The following cellular modem modules are available for the RUGGEDCOM RX1500 series devices. RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Cellular Modem Modules 6.1 RUGGEDCOM RX1500PN LM W11 RUGGEDCOM RX1500PN LM W11 The RUGGEDCOM RX1500PN LM W11 module offers GSM/EDGE/HSPA+ capabilities for wireless remote access to the 3G (third generation) networks in North America (AT&T). It supports a single primary antenna and an optional diversity antenna to improve radio signal strength.
Page 122
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 123
Cellular Modem Modules 6.1 RUGGEDCOM RX1500PN LM W11 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 124
Cellular Modem Modules 6.1 RUGGEDCOM RX1500PN LM W11 Remove the line module from the chassis. For more information, refer to the Installation Manual for the host device. On the smooth side of the module, remove the four screws and separate the cover from the module housing.
Page 125
Cellular Modem Modules 6.1 RUGGEDCOM RX1500PN LM W11 Mount the antenna to a pole or wall in an area that provides good signal coverage and is away from any signal noise emanating from other communications equipment. Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS).
Page 126
Cellular Modem Modules 6.1 RUGGEDCOM RX1500PN LM W11 System/ Frequency Band (MHz) Conducted Tx Comment Operating Band Power (dBm) DCS-1800 and 1800/1900 +29 ± 1 GMSK mode, PCS-19001 connectorized (class 1) +26 ± 1 8PSK mode, connectorized (class E2) Band I 2100 +23 ±...
Page 127
This module has been assigned the Industry Canada product ID 2417C-MC8705. RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Cellular Modem Modules 6.2 RUGGEDCOM RX1500PN LM W12 RUGGEDCOM RX1500PN LM W12 The RUGGEDCOM RX1500PN LM W12 module offers GSM/EDGE/HSPA+ capabilities for wireless remote access to 3G (third generation) networks in North America (AT&T), Europe and Australia. It supports dual primary antennas and optional diversity antennas to improve radio signal strength.
Page 129
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 130
Cellular Modem Modules 6.2 RUGGEDCOM RX1500PN LM W12 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 131
Cellular Modem Modules 6.2 RUGGEDCOM RX1500PN LM W12 Remove the line module from the chassis. For more information, refer to the Installation Manual for the host device. On the smooth side of the module, remove the four screws and separate the cover from the module housing.
Page 132
Cellular Modem Modules 6.2 RUGGEDCOM RX1500PN LM W12 Mount the antenna to a pole or wall in an area that provides good signal coverage and is away from any signal noise emanating from other communications equipment. Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS).
Page 133
Cellular Modem Modules 6.2 RUGGEDCOM RX1500PN LM W12 System/ Frequency Band (MHz) Conducted Tx Comment Operating Band Power (dBm) DCS-1800 and 1800/1900 +29 ± 1 GMSK mode, PCS-19001 connectorized (class 1) +26 ± 1 8PSK mode, connectorized (class E2) Band I 2100 +23 ±...
Page 134
(ACMA) under the Radiocommunications Act 1992 and the Telecommunications Act 1997. RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Cellular Modem Modules 6.3 RUGGEDCOM RX1500PN LM W21 RUGGEDCOM RX1500PN LM W21 The RUGGEDCOM RX1500PN LM W22 module offers EVDO Rev A capabilities for wireless remote access to 3G (third generation) networks in North America (AT&T), Europe and Australia. It supports a single primary antenna and an optional diversity antenna to improve radio signal strength.
Page 136
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 137
Cellular Modem Modules 6.3 RUGGEDCOM RX1500PN LM W21 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 138
Cellular Modem Modules 6.3 RUGGEDCOM RX1500PN LM W21 Remove the line module from the chassis. For more information, refer to the Installation Manual for the host device. On the smooth side of the module, remove the four screws and separate the cover from the module housing.
Page 139
A Radio Frequency (RF) site survey is recommended prior to any installation to help determine the best location for the LTE and GPS antennas. For assistance, contact a Siemens Sales representative. • The cellular modem supports SISO (Single Input Single Output) and MIMO (Multiple Input Multiple Output) modes.
Page 140
Cellular Modem Modules 6.3 RUGGEDCOM RX1500PN LM W21 Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS). RUGGEDCOM RX1500 Shielded Coaxial Cable Lightning Protector Antenna Figure 6.9...
Page 141
This module is certified by Verizon Wireless in North America under Open Development Certification Agreement MA-004198-2012. RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Page 142
China RoHS 2 Administrative Measure on the Control of Pollution Caused by Electronic Information Products A copy of the Material Declaration is available online at https:// support.industry.siemens.com/cs/ww/en/view/109738831. Ordering Information Description 1 x EVDO rev A Verizon US Article Numbers 6GK6015-0AL20-0WD0 (Standard)
Cellular Modem Modules 6.4 RUGGEDCOM RX1500PN LM W22 RUGGEDCOM RX1500PN LM W22 The RUGGEDCOM RX1500PN LM W22 module offers EVDO Rev A capabilities for wireless remote access to 3G (third generation) networks in North America (AT&T), Europe and Australia. It supports dual primary antennas and optional diversity antennas to improve radio signal strength.
Page 144
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 145
Cellular Modem Modules 6.4 RUGGEDCOM RX1500PN LM W22 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 146
Cellular Modem Modules 6.4 RUGGEDCOM RX1500PN LM W22 Remove the line module from the chassis. For more information, refer to the Installation Manual for the host device. On the smooth side of the module, remove the four screws and separate the cover from the module housing.
Page 147
A Radio Frequency (RF) site survey is recommended prior to any installation to help determine the best location for the LTE and GPS antennas. For assistance, contact a Siemens Sales representative. • The cellular modem supports SISO (Single Input Single Output) and MIMO (Multiple Input Multiple Output) modes.
Page 148
Cellular Modem Modules 6.4 RUGGEDCOM RX1500PN LM W22 Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS). RUGGEDCOM RX1500 Shielded Coaxial Cable Lightning Protector Antenna Figure 6.12...
Page 149
This module is certified by Verizon Wireless in North America under Open Development Certification Agreement MA-004198-2012. RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Page 150
China RoHS 2 Administrative Measure on the Control of Pollution Caused by Electronic Information Products A copy of the Material Declaration is available online at https:// support.industry.siemens.com/cs/ww/en/view/109738831. Ordering Information Description 2 x EVDO rev A Verizon US Article Numbers 6GK6015-0AL20-0WE0 (Standard)
Cellular Modem Modules 6.5 RUGGEDCOM RX1500PN LM W32 RUGGEDCOM RX1500PN LM W32 The RUGGEDCOM RX1500PN LM W32 module offers GSM/EDGE/HSPA+ and EVDO Rev A capabilities for wireless remote access to the 3G (third generation) networks in North America(AT&T and Verizon). It supports dual primary antennas and optional diversity antennas to improve radio signal strength.
Page 152
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 153
Cellular Modem Modules 6.5 RUGGEDCOM RX1500PN LM W32 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 154
Cellular Modem Modules 6.5 RUGGEDCOM RX1500PN LM W32 Remove the line module from the chassis. For more information, refer to the Installation Manual for the host device. On the smooth side of the module, remove the four screws and separate the cover from the module housing.
Page 155
Cellular Modem Modules 6.5 RUGGEDCOM RX1500PN LM W32 Mount the antenna to a pole or wall in an area that provides good signal coverage and is away from any signal noise emanating from other communications equipment. Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS).
Page 156
Cellular Modem Modules 6.5 RUGGEDCOM RX1500PN LM W32 Conducted Transmit (Tx) Power Tolerances System/ Frequency Band (MHz) Conducted Tx Comment Operating Band Power (dBm) GSM-850 and GSM-900 850/900 +32 ± 1 GMSK mode, connectorized (class 4) +27 ± 1 8PSK mode, connectorized (class E2) DCS-1800 and 1800/1900...
Page 157
This module is certified by Verizon Wireless in North America under Open Development Certification Agreement MA-004198-2012. RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical...
Page 158
Cellular Modem Modules 6.5 RUGGEDCOM RX1500PN LM W32 Ordering Information Description 2 x GSM/EDGE/HSPA and EVDO rev A Verizon US Article Numbers 6GK6015-0AL20-0WF0 (Standard) 6GK6015-0AL20-0WF1 (Conformal Coated) RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Cellular Modem Modules 6.6 RUGGEDCOM RX1500PN LM W41 RUGGEDCOM RX1500PN LM W41 The RUGGEDCOM RX1500PN LM W41 module offers 4G LTE, HSPA+, HSDPA, HSUPA, DC-HSPA+, UMTS/WCDAM, EDGE, GPRS, GSM and GNSS capabilities for wireless remote access to 4G (fourth generation) LTE (Long Term Evolution) networks in European Union countries.
Page 160
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 161
Cellular Modem Modules 6.6 RUGGEDCOM RX1500PN LM W41 Insert the module into the host device. For more information, refer to the Installation Manual for the device. Connect antennas. Configure the LTE modem and GPS settings. For more information, refer to the RUGGEDCOM ROX Configuration Manual for the host device.
Page 162
Cellular Modem Modules 6.6 RUGGEDCOM RX1500PN LM W41 [Optional] Repeat the steps above to install a second SIM card in Cage 2. Place the cover on the module housing and install the four screws removed previously. Install the module back into the chassis. For more information, refer to the Installation Manual for the host device.
Page 163
Cellular Modem Modules 6.6 RUGGEDCOM RX1500PN LM W41 Region European Union Connector 50 Ω SMA Antennas 1 x LTE Main, 1 x LTE MIMO, 1 x GPS Dual Mini-SIM (2FF) Power Consumption Supported LTE Channel Bandwidths Band Channel Bandwidths (MHz) Band 1 û...
Page 164
Cellular Modem Modules 6.6 RUGGEDCOM RX1500PN LM W41 GNSS Specifications Satellite Channels 12 channel, continuous tracking Protocols NMEA 0183 v3.0 Acquisition Time • Hot start: 1 s • Warm start: 29 s • Cold start: 32 s Accuracy • Horizontal: < 2 m 6.6 ft (50 %), < 5 m or 16.4 ft (90 %) •...
Page 165
Cellular Modem Modules 6.6 RUGGEDCOM RX1500PN LM W41 Band Conducted Rx Sensitivity (dBm) Primary Secondary SIMO (Typical) SIMO (Worst (Typical) (Typical) Case) Band 8 -99.3 -98.5 -102.0 -93.3 Band 20 -99.6 -98.4 -99.8 -93.3 Conducted Rx (Receive) Sensitivity for UMTS Bands Band Error Rate Conducted Rx Sensitivity (dBm)
Page 166
Siemens AG. For contact information, refer to "Contacting Siemens (Page ix)". RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 RUGGEDCOM RX1500PN LM W51 The RUGGEDCOM RX1500PN LM W51 module offers 4G LTE, HSPA+, HSDPA, HSUPA, DC-HSAP+, UMTS/WDCAM, EDGE, GPRS, GSM, CDMA, EVDO and GNSS capabilities for wireless remote access to 4G (fourth generation) LTE (Long Term Evolution) networks in North America.
Page 168
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 169
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 170
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Make sure to take appropriate anti-static precautions before opening the cellular modem module. Note The module only supports mini-SIM cards (2FF size format). If necessary, remove the line module from the chassis. For more information, refer to the Installation Manual for the host device.
Page 171
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS). RUGGEDCOM RX1500 Shielded Coaxial Cable Lightning Protector Antenna Figure 6.21...
Page 172
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Standard Bands Notes Data Rates Uplink • 50 Mbps (20 MHz bandwidth) • 25 Mbps (10 MHz bandwidth) CDMA IS-856 (1xEVDO Release CDMA EVDO • Band Class 0 (Cellular 800 Diversity Release 0 or MHz) support EVDO Release...
Page 173
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Band Frequencies (MHz) Transmit (Tx) Receive (Rx) Band 4 (AWS) 1710 to 1755 2110 to 2155 Band 5 824 to 849 869 to 894 Band 13 777 to 787 746 to 756 Band 17 704 to 716 734 to 746 Band 25...
Page 174
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Sensitivity • Tracking: -161 dBm • Acquisition (Assisted, Non-LTE): -158 dBm • Acquisition (Assisted, LTE): -153 dBm • Acquisition (Standalone): -145 dBm Operational Limits Altitude < 6000 m (3.7 mi) or velocity < 100 m/s (328 ft/s) The lowest GNSS signal level at which the device can detect an in-view satellite 50% of the time when in sequential tracking mode.
Page 175
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Conducted Rx (Receive) Sensitivity for UMTS Bands Band Error Rate Conducted Rx Sensitivity (dBm) Primary Secondary Primary/ (Typical) (Typical) Secondary (Worst Case) Band 1 (UMTS 2100) 0.1% BER -111.0 -110.4 -106.7 Band 2 (UMTS 1900) -111.4 -110.5 -104.7...
Page 176
This module is certified under IC CS-03 Part II, Issue 9 and has been assigned the product ID 2417C-MC7355. RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Page 177
Cellular Modem Modules 6.7 RUGGEDCOM RX1500PN LM W51 Certification Details A copy of the Material Declaration is available online at https:// support.industry.siemens.com/cs/ww/en/view/109738831. Ordering Information Description 1 x 4G/LTE ATT/Rogers/Telus/Bell Article Numbers 6GK6015-0AL20-0WH0 (Standard) 6GK6015-0AL20-0WH1 (Conformal Coated) RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
Cellular Modem Modules 6.8 RUGGEDCOM RX1500PN LM W61 RUGGEDCOM RX1500PN LM W61 The RUGGEDCOM RX1500PN LM W61 module offers 4G LTE, HSPA+, CDMA, EVDO, GPS and GNSS capabilities for wireless remote access to 4G (fourth generation) LTE (Long Term Evolution) networks in North America. It supports dual 4G LTE antennas and a single GPS antenna.
Page 179
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 180
Cellular Modem Modules 6.8 RUGGEDCOM RX1500PN LM W61 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 181
Cellular Modem Modules 6.8 RUGGEDCOM RX1500PN LM W61 Make sure to take appropriate anti-static precautions before opening the cellular modem module. Note The module only supports mini-SIM cards (2FF size format). If necessary, remove the line module from the chassis. For more information, refer to the Installation Manual for the host device.
Page 182
Cellular Modem Modules 6.8 RUGGEDCOM RX1500PN LM W61 Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS). RUGGEDCOM RX1500 Shielded Coaxial Cable Lightning Protector Antenna Figure 6.24...
Page 183
Cellular Modem Modules 6.8 RUGGEDCOM RX1500PN LM W61 Band Frequencies (MHz) Transmit (Tx) Receive (Rx) Band 4 (AWS) 1710 to 1755 2110 to 2155 Band 13 777 to 787 746 to 756 Band 25 1850 to 1915 1930 to 1995 Supported CDMA Frequency Bands Band Frequencies (MHz) Transmit (Tx)
Page 184
Cellular Modem Modules 6.8 RUGGEDCOM RX1500PN LM W61 • Gain in azimuth plane is not desired Average 3D gain > -5 dBi Isolation between GNSS and > 10 dB in all uplink bands LTE Main (Primary) Typical VSWR < 2:5:1 Polarization Any other than LHCP (Left-Hand Circular Polarized) is acceptable.
Page 185
Cellular Modem Modules 6.8 RUGGEDCOM RX1500PN LM W61 Conducted Rx (Receive) Sensitivity for CDMA Frequency Bands Band Standard LImit (dBm) Room Class A (dBm) Notes Typical Extreme Limit (dBm) Band Class 0 CDMA 1X -104 -108 -107 -106.5 CDMA 1 x 0.5% FER, EVDO -105.5...
Page 186
This module is certified by Verizon Wireless in North America under Open Development Certification Agreement MA-004198-2012. RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Cellular Modem Modules 6.9 RUGGEDCOM RX1500PN LM W81 RUGGEDCOM RX1500PN LM W81 The RUGGEDCOM RX1500PN LM W81 module offers GSM, EDGE, GPRS, UMTS, HSPA +, 4G LTE and GNSS capabilities for wireless remote access to 4G (fourth generation) LTE (Long Term Evolution) networks in the Asia-Pacific region. It supports dual 4G LTE antennas and a single GPS antenna.
Page 188
Siemens cellular modem, avoid using the cellular modem in applications where a communication failure could result in damage to equipment or personal injury to persons in the area. Siemens accepts no responsibility for any damages that may result due to wireless disruptions.
Page 189
Cellular Modem Modules 6.9 RUGGEDCOM RX1500PN LM W81 Note If this module is integrated into a portable device, separate approval related to the Specific Absorption Rate (SAR) requirements of FCC Part 2.1093 and IC RSS-102 is required. • Persons in the area must be kept at least 20 cm (8 in) from the antenna at all times.
Page 190
Cellular Modem Modules 6.9 RUGGEDCOM RX1500PN LM W81 Make sure to take appropriate anti-static precautions before opening the cellular modem module. Note The module only supports mini-SIM cards (2FF size format). If necessary, remove the line module from the chassis. For more information, refer to the Installation Manual for the host device.
Page 191
Cellular Modem Modules 6.9 RUGGEDCOM RX1500PN LM W81 Using shielded coaxial cables, connect the antenna to the lightning protector. Make sure the cables are routed away from any noise sources, such as Switch- Mode Power Supplies (SMPS). RUGGEDCOM RX1500 Shielded Coaxial Cable Lightning Protector Antenna Figure 6.27...
Page 192
Cellular Modem Modules 6.9 RUGGEDCOM RX1500PN LM W81 Supported LTE Bandwidths Band 1.4 MHz 3 MHz 5 MHz 10 MHz 15 MHz 20 MHz Band 1 û û ü ü ü ü Band 3 ü ü ü ü ü ü Band 7 û...
Page 193
Cellular Modem Modules 6.9 RUGGEDCOM RX1500PN LM W81 Operational Limits Altitude < 6000 m (3.7 mi) or velocity < 100 m/s (328 ft/s) Either limit may be exceeded, but not both GNSS Standalone Antenna Requirements Frequency Range • Narrow-Band GPS: 1572.42 MHz ± 2 MHz minimum •...
Page 195
Industry Online Support at https://support.industry.siemens.com/cs/ ww/en/view/109748643 RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: China RoHS 2 •...
RUGGEDCOM APE Modules The following RUGGEDCOM Application Processing Engine (APE) modules are available for the RUGGEDCOM RX1500 series devices. RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
RUGGEDCOM APE Modules 7.1 RUGGEDCOM RX1500PN LM APE1402 (Obsolete) RUGGEDCOM RX1500PN LM APE1402 (Obsolete) The RUGGEDCOM RX1500PN LM APE1402 module is a 32-bit computer with Debian Linux® pre-installed and an 8 GB solid-state drive. LEDs The module features the following LEDs: HDD LED PWR LED RESET Button...
Page 198
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.2 RUGGEDCOM RX1500PN LM APE1402W7 (Obsolete) RUGGEDCOM RX1500PN LM APE1402W7 (Obsolete) The RUGGEDCOM RX1500PN LM APE1402W7 module is a 32-bit computer with Windows® Embedded Standard 7 pre-installed and an 8 GB solid-state drive. LEDs The module features the following LEDs: HDD LED PWR LED RESET Button...
Page 201
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.3 RUGGEDCOM RX1500PN LM APE1404 (Obsolete) RUGGEDCOM RX1500PN LM APE1404 (Obsolete) The RUGGEDCOM RX1500PN LM APE1404 module is a 32-bit computer with Debian Linux® pre-installed and a 16 GB solid-state drive. Description HDD LED PWR LED RESET Button USB Port ETH Port DVI-D Video Port...
Page 204
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.4 RUGGEDCOM RX1500PN LM APE1404 ADM (Obsolete) RUGGEDCOM RX1500PN LM APE1404 ADM (Obsolete) The RUGGEDCOM RX1500PN LM APE1404 ADM module is a 32-bit computer with Debian Linux® and CROSSBOW ADM pre-installed. It also features a 16 GB solid-state drive.
Page 207
7.4 RUGGEDCOM RX1500PN LM APE1404 ADM (Obsolete) For more information about CROSSBOW ADM, refer to the RUGGEDCOM CROSSBOW user documentation available through Siemens Customer Support. Installing the Module For information about installing this module, refer to the Installation Manual for the host device.
Page 208
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.5 RUGGEDCOM RX1500PN LM APE1404W7 (Obsolete) RUGGEDCOM RX1500PN LM APE1404W7 (Obsolete) The RUGGEDCOM RX1500PN LM APE1404W7 module is a 32-bit computer with Windows® Embedded Standard 7 pre-installed and a 16 GB solid-state drive. Requirements/Restrictions Chassis • RUGGEDCOM RX1500 •...
Page 210
RUGGEDCOM APE Modules 7.5 RUGGEDCOM RX1500PN LM APE1404W7 (Obsolete) Rebooting/Powering Down the Module Each RUGGEDCOM APE module is powered on automatically when power is supplied to the chassis, but can be powered down independently using the Power button. This button also allows users to reboot the module. NOTICE Whenever possible, power down or reboot the RUGGEDCOM APE through the RUGGEDCOM RX1500 operating system instead of forcing a shutdown or reboot...
Page 211
7.5 RUGGEDCOM RX1500PN LM APE1404W7 (Obsolete) Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.6 RUGGEDCOM RX1500PN LM APE1404CKP (Obsolete) RUGGEDCOM RX1500PN LM APE1404CKP (Obsolete) The RUGGEDCOM RX1500PN LM APE1404CKP module is a 32-bit computer with Check Point GAiA™ OS pre-installed and a 16 GB solid-state drive. LEDs The module features the following LEDs: HDD LED PWR LED RESET Button...
Page 213
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.7 RUGGEDCOM RX1500PN LM APE1808LNX RUGGEDCOM RX1500PN LM APE1808LNX The RUGGEDCOM RX1500PN LM APE1808LNX module is a 64-bit computer with 8 GB RAM, and a 64 GB solid-state drive. It ships with Debian Linux® pre-installed. Requirements/Restrictions Chassis • RUGGEDCOM RX1500 •...
Page 216
Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: China RoHS 2 •...
Page 217
RUGGEDCOM APE Modules 7.7 RUGGEDCOM RX1500PN LM APE1808LNX Ordering Information Description Application Processing Engine, Atom x5-E3940, 8GB RAM, 64GB eMMC, DisplayPort, uSD, USB, Linux Article Numbers 6GK6015-0AL20-0GH0 (Standard) 6GK6015-0AL20-0GH1 (Conformal Coated) RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
RUGGEDCOM APE Modules 7.8 RUGGEDCOM RX1500PN LM APE1808W10 RUGGEDCOM RX1500PN LM APE1808W10 The RUGGEDCOM RX1500PN LM APE1808W10 module is a 64-bit computer with 8 GB RAM, and a 64 GB solid-state drive. It ships with Microsoft Windows® 10 Enterprise 2019 LTSC pre-installed. Requirements/Restrictions Chassis •...
Page 219
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Page 220
RUGGEDCOM APE Modules 7.8 RUGGEDCOM RX1500PN LM APE1808W10 Ordering Information Description Application Processing Engine, Atom x5-E3940, 8GB RAM, 64GB eMMC, DisplayPort, uSD, USB, Windows 10 Article Numbers 6GK6015-0AL20-0GJ0 (Standard) 6GK6015-0AL20-0GJ1 (Conformal Coated) RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
RUGGEDCOM APE Modules 7.9 RUGGEDCOM RX1500PN LM APE1808CKP RUGGEDCOM RX1500PN LM APE1808CKP The RUGGEDCOM RX1500PN LM APE1808CKP module is a 64-bit computer with Check Point GAiA™ OS pre-installed and a 16 GB solid-state drive. Requirements/Restrictions Chassis • RUGGEDCOM RX1500 • RUGGEDCOM RX1501 This module is only compatible with the following chassis.
Page 222
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.10 RUGGEDCOM RX1500PN LM APE1808ADM 7.10 RUGGEDCOM RX1500PN LM APE1808ADM The RUGGEDCOM RX1500 PN LM APE1808ADM module is a 64-bit computer with 8 GB RAM, and a 64 GB solid-state drive. It ships with Debian Linux® and RUGGEDCOM CROSSBOW ADM pre-installed.
Page 225
The ADM must be reachable from the CROSSBOW External Database Integration Service (EDIS). For more information about RUGGEDCOM CROSSBOW ADM, refer to the RUGGEDCOM CROSSBOW user documentation available through Siemens Customer Support. Installing the Module For information about installing this module, refer to the Installation Manual for the host device.
Page 226
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
RUGGEDCOM APE Modules 7.11 RUGGEDCOM RX1500PN LM APE1808SAM-L 7.11 RUGGEDCOM RX1500PN LM APE1808SAM-L The RUGGEDCOM RX1500 PN LM APE1808SAM-L module is a 64-bit computer with 8 GB RAM, and a 64 GB solid-state drive. It ships with RUGGEDCOM CROSSBOW SAM-L pre-installed. Requirements/Restrictions Chassis •...
Page 228
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: RUGGEDCOM Modules...
Page 229
Administrative Measure on the Control of Pollution Caused by Electronic Information Products A copy of the Material Declaration is available online at https:// support.industry.siemens.com/cs/ww/en/view/109738831. Ordering Information Description Application Processing Engine, Atom x5-E3940, 8GB RAM, 64GB eMMC, DisplayPort, uSD, USB, CROSSBOW SAM-L FW...
Blank Modules The following blank modules are available for the RUGGEDCOM RX1500 series devices. NOTICE Blank modules should be installed in empty slots to prevent the ingress of dirt or debris in the chassis. RUGGEDCOM Modules Catalog, 07/2021, C79000-G8976-1320-16...
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
This module has been certified to comply with the requirements of the following standards. Certification Details RoHS This module is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Page 234
Further Information Siemens RUGGEDCOM https://www.siemens.com/ruggedcom Industry Online Support (service and support) https://support.industry.siemens.com Industry Mall https://mall.industry.siemens.com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY...