Siemens NIM-1W Installation Instructions Manual
Siemens NIM-1W Installation Instructions Manual

Siemens NIM-1W Installation Instructions Manual

Network interface module

Advertisement

Quick Links

Installation Instructions
Model NIM-1W Network Interface Module
NETWORK INTERFACE APPLICATIONS
OPERATION
The Model NIM-1W from Siemens Industry, Inc.,
provides a new communication path for the following
uses:
• as an XNET networking interface
• as an HNET connection to NCC WAN
• as a connection to Foreign Systems
• as a connection to Air Sampling detectors
When used as an XNET networking interface the
NIM-1W allows for the connection of up to 63 MXL
and/or XLS Systems. On an XNET network the NIM-
1W also supports monitor and control functionality by
Siemens products, such as NCC and Desigo CC.
Output logic between MXL panels is done using
CSG-M programming. CSG-M versions 6.01 and
higher include options for networked MXL Systems.
Each MXL System is assigned a panel number. This
panel number allows interactive programming be-
tween panels using CSG-M.
INSTALL JUMPER
PLUGS IN ORIENTATION
AS SHOWN. POSITION
M
SHOWN SELECTED.
M
W
JP4
M
W
1
3
JP2
13
15
JP4
D4
SW1
1
8 7 6 5 4 3 2 1
ANY
TRBL
Figure 1
NIM-1W Module Board (RS485 setting)
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-099165-10
NIM-1W
P6
D5
3
15
+
W
ANY
X
ENABLE
1
13
W
X
P6
INSTALL JUMPER PLUGS IN
ORIENTATION AS SHOWN
FOR RS485 WIRING.
POSITION SHOWN
X
SELECTED.
The NIM-1W supports both Style 4 and Style 7
connection. In the event of an NIM-1W communica-
tion failure, each MXL System continues to operate
as a standalone panel.
The NIM-1W can also be configured as an RS-485
two wire interface to foreign systems. NIM-1W
RS485 only supports Style 4 wiring. Via the add-on
modem card NIM-1M, NIM-1W can also be config-
ured for modem connection. This operation is called
FSI (Foreign System Interface). The FSI responds
to a protocol and gathers information about the MXL
status. The interface supports both single MXL
Systems and networked systems. Typical use of
this interface is between the MXL and building
management systems.
Use the CSG-M to enable the functions accessed
by the foreign system. If the foreign system is UL
864 listed with the MXL, the interface can also be
enabled to support control of the MXL including the
commands to acknowledge, silence, and reset.
INSTALL JUMPER
PLUGS IN ORIENTATION
AS SHOWN. POSITION
SHOWN SELECTED.
M
8 7 6 5 4 3 2 1
SW2
13
JP1
D8
XMIT
NIM-1W Module Board (modem setting)
M
W
JP4
NIM-1W
M
W
1
3
JP2
15
JP4
D4
D5
SW1
1
ANY
ANY
8 7 6 5 4 3 2 1
TRBL
ENABLE
Figure 2
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
8 7 6 5 4 3 2 1
SW2
JP1
P6
3
15
D8
+
W
X
1
13
XMIT
W
X
P6
INSTALL JUMPER PLUGS IN
ORIENTATION AS SHOWN
FOR MODEM.

Advertisement

loading

Summary of Contents for Siemens NIM-1W

  • Page 1 When used as an XNET networking interface the FSI (Foreign System Interface). The FSI responds NIM-1W allows for the connection of up to 63 MXL to a protocol and gathers information about the MXL and/or XLS Systems. On an XNET network the NIM- status.
  • Page 2 TABLE 1 NETWORK ADDRESS PROGRAMMING (SW1) 8 76 5 43 21 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 ADDR ADDR ADDR ADDR ILLEGAL OXOOOOOO XOOOOOOO XXOOOOOO...
  • Page 3: Installation

    The 4. Set jumper plugs on P6 to the "X" position (Figure NIM-1W can be installed in either of the full slots of the 1) if using NIM-1W for RS-485 interface. Set MOM-4/2.
  • Page 4 Figure 3 NIM-1W Network Wiring Diagram 5. When installing the NIM-1W for FSI operation, set After setting the switches, install the NIM-1W into the the switch to all open (or OFF). MOM-4/2 card cage. Make sure that the module is in...
  • Page 5: Electrical Connections

    Do not T-tap the network wiring. If T-tapping is required, use the REP-1 repeater. Refer to the REP-1 Figure 3 shows the wiring diagram for the NIM-1W on Installation Instructions, P/N 315-092686, the an XNET network. Up to 32 MXL and/or XLS Sys-...
  • Page 6 NIM-1W/NIM-1M modem FSI connection should be The FSI installs on TB3 or TB4, terminals 1 and 2, of wired Style 4 only. P6 jumper position on the NIM-1W the MOM-4/2 depending on where the NIM-1W is should be set for Modem configuration as shown in installed, as shown in Figure 5.
  • Page 7: Electrical Ratings

    MOM-4/2, TB3 or TB4, terminals 12-16, depending on P/N 315-099200. (Refer to Figure 8.) where the NIM-1W is installed (Refer to Figure 8). Up • To connect the CPY-HLI to the VESDA network, to 31 Air Sampling detectors can be connected to a refer to the CPY-HLI Installation Instructions, P/N single NIM-1W.
  • Page 8 1. 18 AWG minimum. 2. 80 ohms maximum per pair. 3. Use twisted pair or shielded twisted pair. 4. Terminate the shield at the NIM-1W enclosure only. 5. Power limited to NFPA 70 per NEC 760. 6. Maximum voltage 8V peak to peak.