Section 6
Installation
76
Table 30
Settings, continue
Actual
Parameter
value
3Ith> / 49
ϑ0
ϑpowerOFF
Ib
τ
τ
↓s
ϑalm
ϑtrip
ϑstartinhibit
3I/IoBF / 51BF/51NBF
I
cbfp
Io
cbfp
t Retrip
t Backup
O -> I / 79
AR start
mode
CB ready
Shot
Activate t
Pulse tp
Cycle t1
Cycle t2
Cycle t3
Cycle t4
Reclaim tr
Block tb
Default
Unit
Range
value
080
%
0.0...100%
4
-
1...4
1.0
In
0.1 ... 1.5
045
min
1.0...300
045
min
1.0...300
121
%
50...200%,
144
%
50...200%,
105
%
50...200%,
01.1
In
0.2...2.0
01.1
In
0.1...2.0
0.10
s
0.06...0.5
0.12
s
0.06...0.5
1
1 = Trip, 2 = Gen. start and trip
-
1
1 = OCO, 2 = CO
-
3
0...4
-
sec
0.1...5
sec
0.2...20
sec
0.2...300
sec
0.2...300
sec
0.2...300
sec
0.2...300
sec
1...300
sec
1...300
1MDU07212-YN Rev. D
Resolution
1%
1
0.100
1.000
1.000
1%
1%
1%
0.100
0.100
0.010
0.010
1
1
1
0.100
0.100
0.010
0.010
0.010
0.010
1
1