1MDU07212-YN Rev. D
4.7.2.2
4.7.2.3
REF601 / REJ601 / REM601
Application Manual
Table 12
Setting ranges for Auto-reclose function I <-> O, 79, continue
Parameter
Description
Pulse tp
Auto reclose pulse time
Dead time for first auto reclose
Cycle t1
cycle
Cycle t2
Dead time for second auto
reclose cycle
Cycle t3
Dead time for third auto
reclose cycle
Cycle t4
Dead time for fourth auto
reclose cycle
Reclaim tr
Reclaim time
Block tb
Auto reclosure block time.
Configurable inputs to Auto-reclose function
Table 13:
Configurable inputs to Auto-reclose function I <-> O, 79
Name
Type
CB CLOS POS
BOOL
EXT TRIP
BOOL
CB READY
BOOL
Configurable outputs of Auto-reclose function
Table 14:
Configurable Outputs to Auto-reclose function I <-> O, 79
Name
Type
O→I CLOSE
BOOL
O→I IN
BOOL
PROGRESS
FINAL TRIP
BOOL
O→I BLOCKED
BOOL
Protection and Control Function
Range
0.2 ... 20.0 [s]
0.20 ... 300.00 [s]
0.20 ... 300.00
0.20 ... 300.00
0.20 ... 300.00
1 ... 300
1 ... 300
Description
Circuit breaker closed position information
External trip input
Circuit breaker ready information
Description
Closing command from auto reclosure
Reclosing cycle in progress, activated during
reclose time
Final trip from auto reclosure
Auto reclosure blocked
Section 4
Unit
Step
Default
s
0.1
0.2
s
0.01
0.5
s
0.01
0.5
s
0.01
0.5
s
0.01
0.5
s
1
1
s
1
5
25