1MDU07212-YN Rev. D
REF601 / REJ601 / REM601
Application Manual
Thermal characteristic warming condition at diabatic behavior:
2
=
+ ((
)
−
) ∗ (1 −
1
0
0
ϑ
= new value of thermal image
1
ϑ
= present value of thermal image
0
I = maximum value of measured phase currents
I
= base current (rated current/full load current defined by setting).
b
Δt = time interval between ϑ
τ↑ = Heating time constant
Thermal characteristic warming condition at adiabatic behavior:
2
∆
=
+ (
)
∗ (
)
1
0
↑
The value of ϑ
IED is defined by a setting
2. Constant thermal image of protected object:
During this condition, the dissipated heat is equal to heat generated by the current
flowing through the protected object.
The thermal model for this conditions is as follow:
=
1
0
whereas:
2
∗ 100 [ % ]
= (
)
0
ϑ
= new value of thermal image
1
ϑ
= present value of thermal image
0
I = maximum value of measured phase currents
I
= base current (rated current/full load current defined by setting).
b
3. Cooling of protected object:
When the current reduces compared to previous condition or the motor has stopped
it results into cooling of an apparatus.
Cooling condition is defined when:
2
∗ 100 [ % ]
> (
)
0
The thermal model used during cooling condition for standing objects (cable /
transformer / standing motor) is:
2
= (
)
+ (
− (
1
0
Protection and Control Function
∆
−(
)
)
↑
and ϑ
0
1
at the start of the function (i.e. at power on of the
0
∆
2
−(
)
)
) ∗
↓
Section 4
27