Setting Table - ABB Relion 605 Series Applications Manual

Feeder/motor protection and control
Hide thumbs Also See for Relion 605 Series:
Table of Contents

Advertisement

1MDU07212-YN Rev. D
6.9
REF601 / REJ601 / REM601
Application Manual

Setting table

Table 30:
Settings
Actual
Parameter
value
3I> / 51
I>
t>
I> Curve
k
3I>> / 50-1
I>>
t>>
3I>>> / 50-2
I>>
t>>
I0> / 51N
I0>
t0>
I0> Curve
k0
I0>> / 50N
I0>>
t0>>
3I2f> / 68
Inrush
threshold
Ratio Setting
I2> / 46
I2>
tI2>
block protn
I2/I1> / 46PD
I2/I1>
tI2/I1>
block protn
Default
Unit
Range
value
01.50
In
0.1...2.5; infinite
01.00
s
0.04...64
DT, IEC NI, IEC VI, IEC LI, IEC EI, RI,
DT
-
ANSI NI, ANSI VI, ANSI MI, ANSI EI,
0.02 – 1.6
0.2...20; infinite (sensor variant)
04.00
In
0.2...25; infinite (CT variant)
00.30
s
0.04...64
0.2...20; infinite (sensor variant)
10.00
In
0.2...25; infinite (CT variant)
00.03
s
0.03...64
Ext.: 0.01...2.0; infinite
00.05
In
Int.: 0.1...2.0; infinite
01.50
s
0.04...64
DT, IEC NI, IEC VI, IEC LI, IEC EI, RI,
DT
-
ANSI NI, ANSI VI, ANSI MI, ANSI EI,
0.02 – 1.6
Ext.: 0.05...12.5; infinite
04.00
In
Int.: 0.5...12.5; infinite
00.05
s
0.04...64
0.2...25 (sensor variant)
0.50
In
0.2...20 (CT variant)
30%
%
30%...50%,
0.30
In
0.1...1.5
1.00
s
0.1 ... 300
0=No
0
1=Yes
015%
In
10...100%
00.10
s
0.1 ... 64
0=No
0
1=Yes
Section 6
Installation
Resolution
0.001
0.010
-
0.010
0.001
0.010
0.001
0.010
0.001
0.010
-
0.010
0.001
0.010
0.010
5%
0.010
0.100
0.010
0.100
75