Mechanical Construction - Siemens SIPART PS100 Compact Operating Instructions

Electropneumatic positioners
Table of Contents

Advertisement

Pneumatic data
Quality class compressed air according to ISO 8573-1
Solid impurities
Pressure dew point
Oil content
Flow rate
Aerate process drive
Supply pressure 4 bar (58 psi)
Supply pressure 6 bar (87 psi)
Depressurize process drive
Actuating pressure 4 bar (58 psi)
Actuating pressure 6 bar (87 psi)
Leakage actuator chamber (positioner portion)
Consumption at operating medium in the controlled state
Sound pressure level
9.5

Mechanical construction

Mechanical construction
Supported actuator types
Linear actuator, range of stroke
Part-turn actuator, angle-of-rotation range
Weight, positioner without accessories
Material
Lid
Base plate
Torques
Lid fixing screws
Part-turn actuator fixing screws DIN 933 M6x12-A2
Linear actuator fixing screws DIN 933 M8x16-A2
Gland pneumatic G¼
Pneumatic gland 1/4-18 NPT
Without sealant
With sealant
M20 cable gland, plastic
M20 cable gland, metal
Cable gland 1/2-14 NPT metal
SIPART PS100
Compact Operating Instructions, 05/2021, A5E50188940-AA
Class 3
Min. 20 K (36 °F) below ambient temperature
Class 3
7.1 m³/h (31.3 USgpm)
9.8 m³/h (43.1 USgpm)
13.7 m³/h (60.3 USgpm)
19.2 m³/h (84.5 USgpm)
< 6⋅10
m³/h (0.0026 USgpm)
-4
< 3.6⋅10
-2
m³/h (0.158 USgpm)
L
< 75 dB
A eq
L
< 80 dB
A max
10 to 130 mm (0.39 to 5.12")
10 to 100°
Approx. 1.0 kg (2.20 lb)
Aluminum
Polycarbonate
Aluminum
1.5 Nm (1.1 ft lb)
5 Nm (3.7 ft lb)
12 Nm (8.9 ft lb)
15 Nm (11.1 ft lb)
12 Nm (8.9 ft lb)
6 Nm (4.4 ft lb)
4 Nm (3 ft lb)
6 Nm (4.4 ft lb)
15 Nm (11.1 ft lb)
Technical specifications
9.5 Mechanical construction
45

Advertisement

Table of Contents
loading

Table of Contents