Pneumatic data
Supply pressure 4 bar (58 psi)
Supply pressure 6 bar (87 psi)
● Depressurize process drive
Actuating pressure 4 bar (58 psi)
Actuating pressure 6 bar (87 psi)
Leakage actuator chamber (positioner portion)
Consumption at operating medium in the controlled state
Sound pressure level
10.5

Mechanical construction

Mechanical construction
Supported actuator types
● Linear actuator, range of stroke
● Part-turn actuator, angle-of-rotation range
Weight, positioner without accessories
Material
● Lid
● Base plate
Torques
● Lid fixing screws
● Part-turn actuator fixing screws DIN 933 M6x12-A2
● Linear actuator fixing screws DIN 933 M8x16-A2
● Gland pneumatic G¼
● Pneumatic gland 1/4-18 NPT
Without sealant
With sealant
● M20 cable gland, plastic
● M20 cable gland, metal
● Cable gland 1/2-14 NPT metal
● Cable gland for NPT bushing in the NPT adapter
NOTE: To avoid damage to the device, the NPT adapter
must be held in place while the NPT gland is screwed into
the NPT adapter.
● Screw cap made of plastic
● Screw cap made of metal
● Pressure gauge block fixing screws
SIPART PS100
Operating Instructions, 11/2019, A5E45863537-AC
7.1 m³/h (31.3 USgpm)
9.8 m³/h (43.1 USgpm)
13.7 m³/h (60.3 USgpm)
19.2 m³/h (84.5 USgpm)
< 6⋅10
m³/h (0.0026 USgpm)
-4
< 3.6⋅10
m³/h (0.158 USgpm)
-2
L
< 75 dB
A eq
L
< 80 dB
A max
10 to 130 mm (0.39 to 5.12")
10 to 100°
Approx. 1.0 kg (2.20 lb)
● Aluminum
● Polycarbonate
Aluminum
1.5 Nm (1.1 ft lb)
5 Nm (3.7 ft lb)
12 Nm (8.9 ft lb)
15 Nm (11.1 ft lb)
12 Nm (8.9 ft lb)
6 Nm (4.4 ft lb)
4 Nm (3 ft lb)
6 Nm (4.4 ft lb)
15 Nm (11.1 ft lb)
68 Nm (50 ft lb)
2.5 Nm (1.8 ft lb)
4 Nm (3 ft lb)
6 Nm (4.4 ft lb)
Technical specifications
10.5 Mechanical construction