Recycling And Disposal - Riello STEEL PRO POWER Installation, Technical Assistance Service And System Management Manual

Table of Contents

Advertisement

SYSTEM MANAGER
MODBUS CONNECTION
Register
Automatic
Access Description Note
number
conversion
Minimum
value
that
can be
510
X
X
assigned
NV
Yes
to the
heating
set-point
(Par. 23)
Night-time
511
X
X
attenuation
NV
Yes
(Par. 28)
In the "Note" column, the registers marked with "V" can be
written on an ongoing basis (and be used for dynamic size con-
trol). Registers marked with "NV", on the other hand, can be
overwritten only for a limited number of times (around 10,000
times with an average of twice a day).
Service reminder
Access
Register
Automatic
Description
number
conversion
L
S
Hours
elapsed
1500
X
from the last
maintenance
activity
Hours from
the next
1501
X
maintenance
activity
STATUS table
Nr.
Name
Description
0
STANDBY
Standby
10
ALARM
Non-volatile lockout error
14
BLOCK
Volatile lockout error
15
FROST_PROTECT Frost protection on
16
CH_DEMAND
Heat demand
17
RESET_STATE
Reset
STORAGE_DE-
18
DHW demand
MAND
DHW_TAP_DE-
19
Imm. DHW demand.
MAND
20
DHW_PRE_HEAT Pre-heating demand
STORE_HOLD_
21
Holding desired storage temperature
WARM
GENERAL_
22
General pump ON
PUMPING
STATE table
Value
Nr.
Name
Description
range
0
RESET_0
Initialisation of reset variables
1
RESET_1
Reset
2
STANDBY_0
Standby
3
PRE_PURGE
Initialisation of pre-purging variables
Depends
on °C/°F
4
PRE_PURGE_1
Pre-purging
units
5
SAFETY_ON
ON safety relay test
6
SAFETY_OFF
OFF safety relay test
7
IGNIT_0
Initialisation of ignition variables
Depends
on °C/°F
8
IGNIT_1
Start-up
units
9
BURN_0
The module is ON
SHUT_DOWN_
Initialisation of variables to check
10
RELAY_TEST_0
safety devices and gas valve
SHUT_DOWN_
11
Safety and gas valve test relay
RELAY_TEST_1
Initialisation of post-purging varia-
12
POST_PURGE_0
bles
Value
range
13
POST_PURGE_1
Post-purging
Initialisation of heating pump varia-
14
PUMP_CH_0
bles
0...65534
15
PUMP_CH_1
Heating pump
hours
16
PUMP_HW_0
Initialisation of DHW pump variables
17
PUMP_HW_1
DHW pump
18
ALARM_1
Non-volatile lockout error
.. 0...2000
19
ERROR_CHECK
Volatile lockout error
20
BURNER_BOOT
Restart of board
CLEAR_E2PROM_
21
Cancel error E2PROM
ERROR
STORE_BLOCK_
22
Save error
ERROR
23
WAIT_A_SECOND Waiting before entering another state
114
SYSTEM MANAGER

9 RECYCLING AND DISPOSAL

The appliance is manufactured using various materials, such as metal, plastics, and electric and electronic components. At the end
of the life cycle, safely remove the components and dispose of them in a responsible manner, in compliance with the installation
country's applicable environmental legislation.
9
Adequate sorted waste collection, processing and environmentally-friendly disposal contribute to preventing possible nega-
tive impacts on the environment and health and promote the reuse and/or recycling of the materials of which the appliance
consists.
9
Illegal disposal of the product by the owner shall be subject to administrative fines provided for by applicable laws.
RECYCLING AND DISPOSAL
115

Advertisement

Table of Contents
loading

Table of Contents