COMMISSIONING AND MAINTENANCE
The parameters regulating such temperature are:
Par.
Description
No.
Sets the desired flow temperature with heating mode.
3
Active for the heating mode Par. 1 = 0 o 3
Limits the minimum value that can be assigned to the
23
set-point in heating mode (does not apply to heating
mode 4).
Limits the maximum value that can be assigned to the
24
set-point in heating mode (does not apply to heating
mode 4).
Delivery Temp.
(°C)
Tset max (°C)
Par. 24
Setpoint
Par. 03
Par. 23
Tset min (°C)
Outdoor Temp. (°C)
Mode 1
(Climatic functioning with room/heat demand thermostat, vari-
able set point according to the outdoor temperature)
In this case the thermal module operates with a variable set-
point depending on outdoor temperature based on a climatic
curve defined by the following parameters:
Par.
Description
No.
Defines the value of the set point calculated on climat-
109
ic mode (Par. 1 = 1).
Establishes the max. set-point at the minimum out-
19
door temperature for climatic regulation
Establishes the minimum outdoor temperature to
20
which the maximum set-point can be associated for
climatic regulation
Establishes the minimum set-point at the maximum
21
outdoor temperature for climatic regulation
Establishes the maximum minimum outdoor tempera-
22
ture to which the minimum set-point can be associat-
ed for climatic regulation
Limits the minimum value that can be assigned to the
23
set-point in heating mode (does not apply to heating
mode 4).
Limits the maximum value that can be assigned to the
24
set-point in heating mode (does not apply to heating
mode 4).
Defines the temperature at which climatic regulation is
25
switched off
Delivery Temp.
(°C)
Tset max (°C)
Par. 24
Par. 19
Par. 21
Par. 109
Tset min (°C)
Par. 23
Par. 20
Par. 22
Par. 25
Outdoor Temp. (°C)
The demand is activated when the room/heat demand thermo-
stat's contact is closed provided that outdoor temperature does
not exceed the value set by the parameter 25.
if the outdoor temperature is higher than the one set on param-
eter 25 , the burner is stopped even if there is a heat demand.
The climatic curve can also be adjusted in a simpler, more us-
er-friendly way.
Enter the "CH" menu. The following display will appear:
Central Heating (CH)
"
"
Outdoor reset
"
"
Press the ● key to confirm and enter the climatic curve screen.
Outdoor reset
"
"
90
Des. Supply T.
"
"
Bas. Supply T.
"
"
WW Shutdown
0
"
"
Bas. Outd. T.
-15
35
"
"
T Outside [°C]
Des. Outd. T.
"
"
"
"
"Design Supply Temp." and "Design Outdoor Temp." will be dis-
played. To change their value, press the ● key.
Use the ▲ / ▼ keys to modify Design Supply Temp and the
1
◄ / ► keys to change Design Outdoor Temp.
2
Press ● to save changes
3
Use the ◄ / ► keys to select other values.
Repeat steps 1 from 3 to make other changes.
After setting the parameters, press the ESC key to exit the menu.
9
If the outdoor temperature sensor (accessory) is not detect-
ed (not installed or damaged) the system provides a warn-
ing: no. 202
The presence of the warning does not stop the thermal
module allowing a heat request to be carried out at the
maximum setpoint set on the climatic regulation.
68
Mode 2
(Working on climatic mode with attenuation controlled by a
room/heat demand thermostat, variable set point according to
the outdoor temperature)
In this case the thermal module operates with a set-point de-
fined by the climatic curve (which can be set in the same way as
described in Mode 1) depending on outdoor temperature. Heat
demand is actioned independently from whether the room/
heat demand thermostat's contact is closed and stops only
when the outdoor temperature is greater than the one defined
by the parameter 25.
In this mode the parameter 28 defines by how many degrees
the set-point is decreased (attenuation) when the room/ heat
demand thermostat's contact is opened.
Par.
Description
No.
Defines the value of the set point calculated on climat-
109
ic mode (Par. 1 = 1).
Establishes the max. set-point at the minimum out-
19
door temperature for climatic regulation
Establishes the minimum outdoor temperature to
20
which the maximum set-point can be associated for
climatic regulation
Establishes the minimum set-point at the maximum
21
outdoor temperature for climatic regulation
Establishes the maximum minimum outdoor tempera-
22
ture to which the minimum set-point can be associat-
ed for climatic regulation
Limits the minimum value that can be assigned to the
23
set-point in heating mode (does not apply to heating
mode 4).
Limits the maximum value that can be assigned to the
24
set-point in heating mode (does not apply to heating
mode 4).
Defines the temperature at which climatic regulation is
25
switched off
82.0
°C
"
"
40.0
°C
Use the heating mode Par. 1= 2 or 3. Defines how many
28
"
"
degrees the flow set point is lowered.
21.0
°C
"
"
21.0
°C
"
"
-4.0
°C
"
"
Delivery Temp.
(°C)
Par. 24
Par. 19
Par. 21
Par. 28
Par. 23
Par. 20
Mode 3
(Continuous fixed set-point operation with attenuation con-
trolled by room/heat demand thermostat)
In this mode the fixed set-point is adjusted in the same way
as described for Mode 0. The difference consists in the fact that
the demand is always active and the set-point is decreased (at-
tenuation) by the value defined by the parameter 28 when the
room/heat demand thermostat's contact is opened.
Par.
Description
No.
Sets the desired flow temperature with heating mode.
3
Active for the heating mode Par. 1 = 0 o 3
Limits the minimum value that can be assigned to the
23
set-point in heating mode (does not apply to heating
mode 4).
Limits the maximum value that can be assigned to the
24
set-point in heating mode (does not apply to heating
mode 4).
Use the heating mode Par. 1= 2 or 3. Defines how many
28
degrees the flow set point is lowered.
Delivery Temp.
(°C)
Par. 24
Par. 03
Par. 28
Par. 23
9
The outdoor temperature sensor (accessory) is not required
and if connected the outdoor temperature that is measured
does not influence the setpoint that has been set.
Mode 4
(Set-point adjustment based on a 0-10V analogical input)
The parameters that control this mode are the following:
Par.
Description
No.
Sets the minimum delivery temperature value in heat-
110
ing mode (Par. 1) = 4.
Sets the maximum delivery temperature value in heat-
111
Tset max (°C)
ing mode (Par. 1) = 4.
The operation set-point is adjusted on the basis of the following
Par. 109
curve:
Temperature
Par. 109
(°C)
Tset min (°C)
Par. 111
Par. 22
Par. 25
Outdoor Temp. (°C)
Par. 110
0
OFF
69
COMMISSIONING AND MAINTENANCE
Tset max (°C)
Setpoint @TA=ON
Attenuation setpoint
@TA=OFF
Tset min (°C)
Outdoor Temp. (°C)
1.0
1.5
2.0
10
ON/OFF
ON
Voltage (V)
Hysterese