COMMISSIONING AND MAINTENANCE
Heating programming
Group
1
"
"
Program Comfort Period
1
"
"
Comfort Setpoint
28.0
°C
"
"
"
"
ECO Setpoint
20.0
°C
"
"
"
"
Out of interval setpoint
Reduced
"
"
"
"
It supports adjusting the time programme for the CH zones with
the following parameters:
Period setting
Enables the user to select a period from 1 to 7. Period settings
enable the user to adjust the active periods for this zone.
− Active days: Selection of the day (s) on which the period
is active. Enables the user to disable the period set for
one or more days. When this parameter is set as inac-
tive, the other items on this menu are no longer used
and hidden from the view. The choice of active days is
between the following macro-groups: Sat-Sun, Mon-Fri,
Mon-Sun, or individual days: Mon, Tue, Wed,...
− Interval 1 (hidden if Active Days is disabled): This param-
eter allows the user to regulate the starting and end time
of the period. The starting time must always be before
the finishing time.
− Interval 2 (hidden if Active Days is disabled): Same as
interval 1. Interval added for the activated period.
− Interval 3 (hidden if Active Days is disabled): Same as
interval 1. Interval added for the activated period.
Group
External Zone
1
CH -
Period
1
"
"
"
"
"
"
Active Day(s)
Program Comfort Period
Sunday
71
"
"
"
"
"
"
Interval 1
Comfort Setpoint
00:00
28.0
00:00
°C
"
"
"
"
"
"
ECO Setpoint
Interval 2
00:00
20.0
00:00
°C
"
"
"
"
"
"
Out of interval setpoint
Interval 3
00:00
00:00
Reduced
"
"
"
"
"
"
Comfort Set-point
Comfort temperature to be used when the zone is in a certain
period. (10 -30 °C).
ECO set-point
ECO temperature. Adjustable temperature that can be used out-
side set periods (5 – 20 °C).
Set-points outside the interval
Selection of the type of set-point to be used when a zone is not
on a set period by selecting between:
− Off
− Comfort
− Eco
− Anti-Freeze (is activated below 5°C NON-ADJUSTABLE)
− Reduced (Calculated as -10°C Comfort Set-point value)
DHW setting
Group
1
"
"
Program Comfort Period
1
"
"
Out of interval setpoint
On
"
"
"
"
It supports adjusting the time programme for the DHW zone.
Period setting
Enables the user to select a period from 1 to 7. Period settings
enable the user to adjust the active periods for this zone.
− Active days: Selection of the day (s) on which the period
is active. Enables the user to disable the period set for
one or more days. When this parameter is set as inac-
tive, the other items on this menu are no longer used
and hidden from the view. The choice of active days is
between the following macro-groups: Sat-Sun, Mon-Fri,
Mon-Sun, or individual days: Mon, Tue, Wed,...
− Interval 1 (hidden if Active Days is disabled): This param-
eter allows the user to regulate the starting and end time
of the period. The starting time must always be before
the finishing time.
− Interval 2 (hidden if Active Days is disabled): Same as
interval 1. Interval added for the activated period.
− Interval 3 (hidden if Active Days is disabled): Same as
interval 1. Interval added for the activated period.
External Zone
Group
DHW
DHW -
Period
1
"
"
"
"
"
"
Program Comfort Period
71
Active Day(s)
Sunday
"
"
"
"
"
"
Interval 1
Comfort Setpoint
00:00
00:00
28.0
°C
"
"
"
"
"
"
Interval 2
ECO Setpoint
00:00
00:00
20.0
°C
"
"
"
"
"
"
Interval 3
Out of interval setpoint
00:00
00:00
Reduced
"
"
"
"
"
"
Set-points outside the interval
Selection of the type of set-point to be used when a zone is not
on a set period by selecting between:
− Off
− On
72
Holiday setting
Holiday Settings
"
"
Mode
Group
"
"
"
"
Group
1
"
"
Enables the user to change parameters for the Holiday Pro-
gramme.
Mode
Select the Holiday programme mode. It can be set to Off, System
or group.
Off
Disabled programme
Group
it enables the selection of the group (1 – 8).
As part of group selection, the Holiday Group is displayed with
the following parameters:
− Holiday set-point: Set-point type to be used for the se-
lected group. All zones in this group shall use this set-
point if the current date is between the start and end
date of the holiday period, but only if the group is en-
abled in the group settings menu, and can be selected
from: Off, Comfort, Eco, Anti-freeze and Reduced.
− Start date / End date (Day DD-MM-YEAR):
Group
External Zone
DHW
DHW -
Period
1
"
"
"
"
"
"
Program Comfort Period
Active Day(s)
Sunday
71
"
"
"
"
"
"
Interval 1
Comfort Setpoint
00:00
00:00
28.0
°C
"
"
"
"
"
"
ECO Setpoint
Interval 2
00:00
20.0
00:00
°C
"
"
"
"
"
"
Interval 3
Out of interval setpoint
00:00
00:00
Reduced
"
"
"
"
"
"
− System: It enables the user to select the holiday pro-
gramme for the entire system. In this mode, the set-
point is common to all system groups.
Group
External Zone
DHW
DHW -
Period
1
"
"
"
"
"
"
Active Day(s)
Program Comfort Period
Sunday
71
"
"
"
"
"
"
Comfort Setpoint
Interval 1
00:00
00:00
28.0
°C
"
"
"
"
"
"
ECO Setpoint
Interval 2
00:00
20.0
00:00
°C
"
"
"
"
"
"
Interval 3
Out of interval setpoint
00:00
Reduced
00:00
"
"
"
"
"
"
− Holiday set-point (hidden if the Mode is set to "Off"):
Type of reference to be used when system mode is select-
ed. This set-point is used for all areas. Only used for the
holiday system.
COMMISSIONING AND MAINTENANCE
Seasonal setting
Enables the user to change parameters for the Seasonal Pro-
gramme.
The seasonal programme is used to define a period of inactivity
for the heating system. This menu includes the following ele-
ments:
Activates heating basis
Selects how the seasonal programme must verify whether heat-
ing can be allowed or not. It can be set on:
− Always: it means that the seasonal programme is ignored
and (CH) heat demand is always allowed throughout the
year.
Season Settings
"
"
Mode
Off
"
"
"
"
− At date: excludes heating (CH+zone) when the current
date is included between the start and the end dates.
Season Settings
"
"
Mode
On Date
"
"
"
"
Begin Date
15-04
"
"
End Date
15-09
"
"
− At Temp: excludes heating (CH+zone) when the outdoor
temperature is higher than the selected temperature.
(Ext. deactivation T: 0.0 °C/50 °C)
Season Settings
"
"
Mode
On Temp
"
"
"
"
Outdoor Temp. Below
25.0
°C
"
"
"
"
73