Parameters' List - Riello STEEL PRO POWER Installation, Technical Assistance Service And System Management Manual

Table of Contents

Advertisement

INSTALLATION
58
2.14.2

Parameters' list

Parameters are listed base on the reference menu.
Reference Menu
M1
Parameters Menu
M2
Cascaded module configuration menu
M3
Cascaded boiler configuration menu
M4
Appliance configuration menu
Display
Menu Par.
visualis-
Description
No.
ation
CH mode Defines the thermal module's various heating opera-
M1
1
tion modes.
CH set-
Defines the desired delivery temperature in heating
M1
3
point
mode (Par. 1) = 0.
Calc.
Establishes the set-point offset value calculated in
M1
109
set-point
climatic mode (Par. 1= 1). Offsets the climatic curve in
off-set
presence of mild outdoor temperatures.
CH Min.
Sets the minimum delivery temperature value in
M1
110
Set-point
heating mode (Par. 1) = 4.
CH Max.
Sets the maximum delivery temperature value in
M1
111
Set-point
heating mode (Par. 1) = 4.
Sets the overrun time in seconds of the boiler's
Boiler
circulator during stand-alone operation; cascaded
M1
5
Pump
operation determines the module's overrun after
Overrun
switch-off due to temperature control.
Sets the activation temperature when the maximum
flue gas temperature is exceeded. When the flue gas
temperature is higher than a set value, the mod-
Flue
ule switches off and an error message is generated.
M1
6
Temp.
When the flue gas temperature is in the interval
Limit
between (Par. 6) -5°C and Par. 6, the module reduces
its power in a linear way until it reaches minimum
power when the temperature measured is equal to
Par. 6.
CH Hys-
Sets the value in degrees beyond the set-point at
M1
7
teresis
which the burner switches off for thermoregulation.
CH Hys-
Sets the value in degrees below the set-point at
M1
112
teresis
which the burner switches on again for thermoreg-
Down
ulation.
Sets the stand-by time before the appliance is
switched on again after it switches off due to ther-
Anti-cy-
M1
9
moregulation, independently from the delivery tem-
cle Period
perature dropping below the value indicated in Par.
10. Parameter valid only in stand-alone mode.
Anti-cy-
Sets the value in degrees below which the burner
M1
10
cle Temp.
switches on again notwithstanding from the time
Diff.
spent at Par. 9.
Sets the value of the temperature difference (Delta T)
between the module's delivery and return temper-
ature. For a Delta T value ranging between Par. 12
and (Par. 12) +8°C, the module reduces its power in a
Hx diff.
linear fashion until it reaches the minimum power.
M1
12
Minimum
The minimum power is maintained until reaching
(Par. 12) +8°C+5°C, after which the module switches
off for a period of time equal to the value attributed
to Par. 13; at the end of this time interval, the module
switches on again.
INSTALLATION
Access type
U
End user
I
Installer
O
Manufacturer
Default
Access
Range
UM
setting
type
0...5
0
I
Par. 23...Par. 24
70
°C
U
Off, -10...10
0
I
20...50
30
°C
I
50...90
80
°C
I
0...900
60
Sec.
I
10...120
100
°C
O
0...20
5
°C
I
0...20
5
°C
I
10...900
120
Sec.
I
0...20
16
°C
I
10...60
40
°C
O
59
Category
Heating
Heating
Heating
Heating
Heating
Heating
General
Heating
Heating
Heating
Heating
General