Temporary Or Short-Term Shut-Down; Preparing For Extended Periods Of Disuse; Replacing And Configuring The Display Board - Riello STEEL PRO POWER Installation, Technical Assistance Service And System Management Manual

Table of Contents

Advertisement

COMMISSIONING AND MAINTENANCE
3.7

Temporary or short-term shut-down

In the event of temporary or short-term shut-down (e.g. due to
holidays), proceed as follows:
− Press the MENU key and select with keys ▲ / ▼ "Time
schedule", confirm with key ●.
− Select with keys ▲ / ▼ "Holiday Schedule" and confirm
with key ●.
− Select with keys ▲ / ▼ "Mode" and confirm with key ●.
Select "System" mode and confirm.
Clock Program
"
"
Program Group
"
"
Burn hours till service
"
"
Reset Service Reminder
"
"
Holiday Settings
"
"
Holiday Settings
"
"
Mode
System
"
"
"
"
Holiday Setpoint
Comfort
"
"
"
"
Begin Date
Saturday
01-08-2015
"
"
"
"
End Date
Saturday
01-08-2015
"
"
"
"
− Select with keys ▲ / ▼ "Holiday Setpoint" and confirm
with key ●.
− Select "Antifreeze" holiday setpoint and confirm.
Holiday Settings
"
"
Mode
System
"
"
"
"
Holiday Setpoint
Anti Fr
"
"
"
"
Begin Date
Saturday
01-08-2015
"
"
"
"
End Date
Saturday
01-08-2015
"
"
"
"
3.8

Preparing for extended periods of disuse

The following operations shall be necessary if the thermal mod-
ule is not used for a long period of time:
− turn the main switch of the thermal modules and the
main system switch to "off"
− Close the fuel and water valves for the heating and do-
mestic hot water system.
9
Empty the thermal and sanitary system if there is a danger
of frost.
82
3.9

Replacing and configuring the display board

9
System configurations must be performed only by the Tech-
nical Assistance Service or by personnel authorized by
After the control panel has been replaced, the next time the de-
vice is restarted, the initial screen is shown.
The system performs a consistency check between the config-
uration data saved on the motherboard and those saved in the
user interface; therefore, when replacing the control interface,
the system can detect an inconsistency between the saved data.
Set the Par. 97 and the Par. 98.
Proceed as follows:
− On the home screen of the control panel, press the ● key
− Select "Settings" with the ▲ / ▼ keys and press the ● key
− Select "Device configuration" with the ▲ / ▼ keys and
press the ● key
Settings
"
"
General Settings
"
"
Boiler Settings
"
"
Appliance Configuration
"
"
− Enter the password as described in paragraph "Password
access"
− Select the unit between "Master" and "Dep1 ... N"
− Select "(97) IO Configuration" and press the ● button
− With the ▲ / ▼ keys change the value following what is in
the following table and press the ● key:
Version
Par. 97
Master, pump version
14
Master, valve version
15
Dependent, pump version
16
Dependent, valve version
17
− Press the ▼ key, select "(98) Appliance Settings" and
press the ● key
Appliance Configuration
"
"
(97) IO Configuration
14
"
"
(98) Appliance Settings
2
"
"
Configuration Confirmed
No
"
"
"
"
COMMISSIONING AND MAINTENANCE
− With the ▲ / ▼ keys change the value following what is in
the following table and press the ● key:
Model
methane
methane
STEEL PRO POWER 114-2 P
R
.
LPG
methane
STEEL PRO POWER 140-2 P
LPG
methane
STEEL PRO POWER 180-2 P
LPG
methane
STEEL PRO POWER 230-2 P
LPG
methane
STEEL PRO POWER 270-2 P
LPG
methane
STEEL PRO POWER 300-3 P
LPG
methane
STEEL PRO POWER 345-3 P
LPG
methane
STEEL PRO POWER 405-3 P
LPG
methane
STEEL PRO POWER 460-4 P
LPG
methane
STEEL PRO POWER 540-4 P
LPG
− Press the ▼ key, select "Config. Confirmed" and press the
● key
− With the ▲ / ▼ keys change the value to "Yes" and press
the ● key
Appliance Configuration
"
"
(97) IO Configuration
14
"
"
(98) Appliance Settings
4
"
"
Configuration Confirmed
Yes
"
"
"
"
At this point the systems starts an application update process.
Once this is finished, the menu "Settings" appears on the menu.
− Press ◄ until you return to the home screen
An error message is displayed for a few seconds and then the
display returns to its normal state.
83
Par. 98
11
12
9
10
7
8
3
4
1
2
5
6
3
4
1
2
3
4
1
2

Advertisement

Table of Contents
loading