YASKAWA VS mini J7 Replacement Instructions Manual page 10

Hide thumbs Also See for VS mini J7:
Table of Contents

Advertisement

Drive
Function/
Parameter
Parameter
No.
Min. output frequency
n14
Min. output voltage
n15
Acceleration time 1
n16
Deceleration time 1
n17
Acceleration time 2
n18
Deceleration time 2
n19
S-curve at accel. Start
S-curve at accel. End
n20
S-curve at decel. start
S-curve at decel. end
Multi speed ref. 1
n21
Multi speed ref. 2
n22
Multi speed ref. 3
n23
Multi speed ref. 4
n24
Multi speed ref. 5
n25
Multi speed ref. 6
n26
Multi speed ref. 7
n27
Multi speed ref. 8
n28
Jog frequency
n29
Frequency reference
n30
upper limit
Frequency reference
n31
lower limit
Motor rated current
n32
Motor overheat
n33
protection
Motor protection time
n34
constant
Drive cooling fan
n35
operation selection
Terminal S1 function
selection
J7
Parameter
Initial Value
No.
1.5Hz
E1-09
12 V *
E1-10
10.0 s
C1-01
10.0 s
C1-02
10.0 s
C1-03
10.0 s
C1-04
0 (0 s)
C2-01
0 (0 s)
C2-02
0 (0 s)
C2-03
0 (0 s)
C2-04
0.0Hz
d1-01
0.0Hz
d1-02
0.0Hz
d1-03
0.0Hz
d1-04
0.0Hz
d1-05
0.0Hz
d1-06
0.0Hz
d1-07
0.0Hz
d1-08
6.0Hz
d1-17
100%
d2-01
0%
d2-02
-
E2-01
0
L1-01
8min
L1-02
0
L8-10
-
-
H1-01
VAN-V07007E  [J7→J1000] Replacement Instructions
J1000
Initial Value
1.5 Hz
* Values for a 400 V class drive are double.
12.0 V *
10.0 s
10.0 s
10.0 s
10.0 s
J7:
0.2 s
Selection parameter (setting 0,1,2, and 3).
Same setting for all conditions.
0.2 s
J1000:
0.2 s
Numerical parameter (time must be set in
seconds). S-curve set separately for each
0.0 s
ride profile section.
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
6.00Hz
100.0%
0.0%
Depends on the drive capacity
-.
J7
n33→0
1
n33→1
n33→2
Set L1-02 = n34 / 8.
1.0 min
J7
n35→0
0
n35→1
The function of S1 is fixed to Fwd Run in
the J7. The equivalent setting in the
40
J1000 is H1-01=40 (default).
Comments
J1000
L1-01→1
L1-01→2
L1-01→0
J1000
L8-10→0
L8-10→1
10/16

Advertisement

Table of Contents
loading

This manual is also suitable for:

J1000