EN
WA R N I N G
!
ALWAYS ensure that high voltage is OFF before
flushing the spray applicator with solvent. NEVER
flush the spray applicator with high voltage ON, as this
is a severe fire hazard and risk to personnel safety.
It is recommended that the high voltage control
be interlocked with the solvent flush signal so that
high voltage is automatically locked out whenever
flushing occurs. Consult your authorized Ransburg
representative for information on interlocking the
high voltage OFF signal with the solvent flush signal.
As outlined in NFPA-33, OSHA, and EN 50176, the AC
power line must be series interlocked with both the exhaust
fan and conveyor.
To install the Controller interlocks perform the following:
1. Turn the 9060 Controller off, disconnect it from its
AC source, and remove the fuses.
2. Open the Controller cabinet door.
CP-13-06-R5 (09/2018)
ALWAYS double check that the Controller is
unplugged from its AC outlet before working with
any internal wiring.
3. Using a small blade screwdriver, remove the factory
installed test jumper from TB1-L2 to TB1-L3.
4. Using a shielded cable for the interlock wiring (supplied
by user), route through the interlock connector on the
side of the 9060 Controller and terminate TB1-L2 and
TB1-L3 as shown in Figure 12. The shielded cable
must have a minimum rating of 300V and 105°C and
its conductors should be 0.8mm
Secure the cable to the interlock connector as described
in "I/O Connections" in the "Installation" section of this
manual so that the shield of the cable is connected to
the chassis of the enclosure.
5. Secure the cabinet door, replace the fuses, and recon-
nect the AC source.
Figure 12: Controller Schematic
19 / 34
INSTALLATION
WA R N I N G
!
(18 AWG) minimum.