Terminal Board And Grounding; Terminal Boxes, End Shields, Grounding Conductors, Sheet Metal Fan Covers - Siemens SIMOTICS SD 1LE5 Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

Technical specifications
B.1 Tightening torques
B.1.2

Terminal board and grounding

Table B- 2
Tightening torques for electrical connections on the terminal board and grounding
Thread ∅
M 3.5
min
0.8
Nm
Max.
1.2
B.1.3

Terminal boxes, end shields, grounding conductors, sheet metal fan covers

If no other tightening torques are specified, then the values in the following table apply.
Table B- 3
Tightening torques for screws on the terminal box, end shields, screw-type grounding conductor connections
Thread ∅
M 3.5
Nm
min
0.8
max
1.2
126
M 4
M 5
0.8
1.8
1.2
2.5
M 4
M 5
M 6
2
3.5
6
3
5
9
M 6
M 8
2.7
5.5
4
8
M 8
M 10
16
28
24
42
Operating Instructions, 10/2020, A5E41454666A
M 10
M 12
9
14
13
20
M 12
M 16
46
110
70
165
1LE5, 1PC4 shaft height 315/355
M 16
27
40
M20
225
340