Operation Checks; Control Settings; Spillage Check; Dress Guard Fitting - Valor SunFire Oxysafe 326 Installer's Manual

Radiant / convector gas fire
Hide thumbs Also See for SunFire Oxysafe 326:
Table of Contents

Advertisement

5.1.
CHECK CONTROL SETTINGS
5.1.1
Depress the control knob and turn
anticlockwise partially towards the 1/IGN position until
some resistance is felt. Keep depressed at this position
for a few seconds to purge air from the system then,
while keeping it depressed, turn fully to the 1/IGN
position. A spark should be generated at the pilot while
turning. The spark should ignite the pilot.
5.1.2.
When pilot ignition has been achieved, keep the
control knob depressed for approximately ten seconds to
allow the thermocouple probe to warm up and then
release it. If the pilot does not remain alight, ensure that
the air has been purged, that the pilot orifice is clear and
that the thermocouple connections are sound. Replace
the pilot unit if necessary (see servicing section of this
manual).
5.1.3.
Check all the control settings. These are:-
Knob
Position
2
Centre radiant on low.
Outer radiants off.
3
Centre radiant on full.
Outer radiants off.
4
Centre radiant on full.
Outer radiants on low.
5
All radiants on full.
5.2.

SPILLAGE CHECK

A spillage check must be made before leaving the installed
appliance with the customer.
5.2.1
Close all doors and windows in the room
containing the appliance.
5.2.2
Light the appliance and set the control knob to
the maximum position (Position 5).
5.2.3
Leave the appliance on for five minutes.
5.2.4
Place the smoke match tube horizontally under
the top lip of the radiant box and at least 50mm away
from the sides of the radiant box. See figure 8.
The installation is satisfactory if the smoke is drawn into
the appliance. If the smoke is not drawn into the
appliance, leave the appliance alight at the maximum
setting for a further ten minutes and then repeat the test.
If the smoke is still not drawn into the appliance, inspect
the sealing of the closure plate. If the sealing is
satisfactory but the appliance is installed with the flue
restrictor (see section 3.3.8), remove the restrictor, reseal
the appliance and retest. If smoke is still not drawn into
the appliance Disconnect the appliance and seek expert
advice.
5.2.5
If the above test is satisfactory, open all internal
connecting doors, hatches, etc. in the room. Keep all
doors and windows that open to the outside of the
building closed. recheck for spillage as above. If an
extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does
10
5. FULL OPERATING CHECKS
Figure 8. Smoke match tube position
not occur with the fan operating and all doors and other
openings between the fan and the appliance open. If the
smoke is drawn into the appliance, continue with the
installation. If the test is not satisfactory, Disconnect the
appliance and advise the customer of the cause of failure.
5.3.
FIT THE DRESS GUARD
Locate the bottom of the dress guard in the two holes in
the apron. Engage the two spring projections at the top
of the guard in the slots under the front canopy.