Wiring Instructions for the SARGENT 2408 Series FIREGUARD
Combination Door Closer-Holder and Releasing Device
with Integral Smoke Detector
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
IMPORTANT NOTE: Fire Alarm Control Panels that cannot ignore a 0.5 second closure during a
power cycle, cannot be used with a 12- Fireguard (smoke detector) product revision "D" and lower.
For more information, see page 7 or contact SARGENT Technical Support at 1-800-810-WIRE(9473).
1. DISCONNECT ALL POWER BEFORE BEGINNING
INSTALLATION TO PREVENT ELECTRICAL SHOCK AND
EQUIPMENT DAMAGE
2. INSTALLER MUST BE A TRAINED EXPERIENCED
SERVICE PERSON
• Wire 12- stand alone unit to appropriate power supply and fire alarm. Earth ground wire connects to green track wire
• Refer to data sticker for proper input voltage and current specifications required
• Energize power supply. Current draw of .1 AMP per unit
• 9- Companion units are designed to work with 12- smoke detector units (12-2468, 12-2478, 12-2498) only
• Wire companion unit to smoke detector unit as shown on wiring diagram
• Do not disconnect any existing wires on smoke detector unit's terminal strip
• Energize power supply
• Open door(s) to hold-open point.
Door(s) should hold open
• Depress on/off test switch on circuit board.
Door(s) should close and latch
• Adjustment of closer spring power may be
necessary to ensure proper latching
• Depress on/off test switch to reactivate
hold open latch assembly(s)
• Adjust holding tension as required
Wiring Optional Remote Push Button
Wiring 12- Units with and without 9- Companion Unit
User supplied normally
closed momentary switch
Remove jumper and install
output connector assembly
(Part No. 63-2868) required
for this option
CAUTION
3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL
ELECTRICAL CODES, ORDINANCES AND REGULATIONS
4. MAXIMUM WIRE SIZE IS 18AWG
5. SEE IMPORTANT NOTE AT END OF PAGE 7
Copyright © 2008 SARGENT Manufacturing. All rights reserved.
Reproduction in whole or in part without the express written
®
INSTALLER:
LEAVE INSTRUCTIONS
WITH BUILDING OWNER
permission of SARGENT Manufacturing is prohibited.
1
A7699C

Advertisement

loading

Summary of Contents for Assa Abloy Sargent FIREGUARD 2408 Series

  • Page 1 Wiring Instructions for the SARGENT 2408 Series FIREGUARD ® Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE. For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com INSTALLER: IMPORTANT NOTE: Fire Alarm Control Panels that cannot ignore a 0.5 second closure during a LEAVE INSTRUCTIONS...
  • Page 2: Connection List

    Smoke Detector Operation and Application The closer/holder unit includes a 4-wire, photoelectric type smoke detector. It provides: smoke detection, door holder latch control, N.O. alarm contact, N.C. supervisory contact and interconnection to other smoke detectors. Field option: one form C auxiliary contact (cut jumper Connection List wire between 11 and 12).
  • Page 3: Checkout Procedure

    Checkout Procedure 1. Turn the power to the unit “On”. Red LED pilot light should illuminate at 8 sec. intervals 2. Open door to the hold open point. The door should hold open. Manually pull door out of hold open and release. Door should close 3.
  • Page 4: Interconnection Wiring Diagram

    Interconnection Wiring Diagram • Use terminals 4 and 15 to wire detectors in parallel (See #1, #2 and #3) • Use terminal 10 to signal remote detectors with relay contact only (See #4 and #5) • Five detectors maximum • Accessory wire pack 63-3212 needed for unit interconnection Remote Detector...
  • Page 5 Typical 12- Wiring with Alarm Panel Monitoring (Class A) 4-Wire System by Others • The alarm circuit monitors if smoke is detected Connect to • The detector trouble circuit monitors if there is a power loss power source 24VAC/DC or 120VAC. Power supply board Power and power source...
  • Page 6 Typical Wiring with Alarm Panel Monitoring (Class B) 2-Wire System • The alarm and trouble circuit monitors if smoke is detected Connect to power source 24VAC/DC or 120VAC. Power supply board and power source Power must match Supply 24VDC @ 0.15A Max. Board to external alarm 24VDC...
  • Page 7 WARNING These fire protection devices require correct wiring A detector may not detect a fire developing on to function. It is the responsibility of the purchaser another level of a building. For this reason, to provide qualified correct wiring installation. detectors should be located on every level of a SARGENT accepts no responsibility for incorrect building.
  • Page 8 Copyright © SARGENT Manufacturing. All rights reserved. Reproduction in whole or in part without the express written permission of SARGENT Manufacturing is prohibited. ASSA ABLOY is the global leader in door opening solutions, dedicated to A7699C-4/08 satisfying end-user needs for security, safety and convenience.
  • Page 9 WARNING These fire protection devices require correct wiring A detector may not detect a fire developing on to function. It is the responsibility of the purchaser another level of a building. For this reason, to provide qualified correct wiring installation. detectors should be located on every level of a SARGENT accepts no responsibility for incorrect building.