Wiring Instructions for the Sargent 2409 Series
®
FIREGUARD Combination Door Closer-Holder and
Releasing Device with Integral Smoke Detector
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY
RESULT IN INJURY OR DAMAGE.
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
"12-2409" Master Unit shown
24VDC "2409" Support Unit shown
1. Disconnect all power before beginning installation
to prevent electrical shock and equipment
damage.
2. Installer must be a trained, experienced service
person.
· Power input to unit must be of the same voltage as that listed on the product label:
·
24VDC for systems where the power input to both the integral smoke detector and the door holder
solenoid is supplied from the same circuit (see Pages 4 and 6 thru 8 of these instructions).
Single Doors
FIREGUARD Series
Use one "12-2409" Master Unit each door
or one "2409" Support unit each door
Pairs of Doors
Power Track Series
Use one "12-2409" Master Unit and
one "2409" Support Unit for each door leaf
(24VDC "2409" Support Unit must be used with "12-2409" Master Unit)
CAUTION:
REQUIREMENT:
®
®
24VDC "2409" Support Unit shown
"12-2409" Master Unit shown
3. All wiring must comply with applicable local
electrical codes, ordinances, and regulations.
4. Maximum wire size is 18AWG.
5. These units are not to be used in limited open
area applications.
Copyright © 2015, Sargent Manufacturing Company, an ASSA ABLOY Group
company, All rights reserved. Reproduction in whole or in part without the
express written permission of Sargent Manufacturing Company is prohibited.
INSTALLER:
LEAVE
INSTRUCTIONS WITH
BUILDING OWNER
A8200 (10/15)