Setting The Learn Cycle Properties - IBM ServeRAID M5014 User Manual

Sas/sata controllers
Table of Contents

Advertisement

6.1.3.2

Setting the Learn Cycle Properties

6-12
battery learn cycles, enable automatic learn cycles. To choose manual
battery learn cycles, disable automatic learn cycles.
If you enable automatic learn cyles, you can delay the start of the learn
cycles for up to 168 hours (7 days). If you disable automatic learn cycles,
you can start the learn cycles manually, and you can choose to receive
a reminder to start a manual learn cycle.
To set the learn cycle properties, perform the following steps:
1. Click the Physical tab to open the physical view.
2. Select the BBU icon in the left panel.
3. Click the Go To > BBU > Set Learn Cycle Properties.
The BBU operations screen appears.
4. Select one of the two automatic learn cycles:
Select the Enable radio button to enable an automatic learn
cycle.
Select the Disable radio button to disable an automatic learn
cycle.
5. You can delay the start of the next learn cycle up to 7 days (168
hours) by specifying the hours in the Delay scheduled learn cycle
by field.
6. Select the Remind me when to start a learn cycle check box tor
receive a reminder to start a manual learn cycle.
Note:
After you select Disable, if you then select Enable, the
controller firmware resets the battery module properties to
initiate an immediate battery learn cycle. The Next Learn
cycle field is not updated until the battery relearn is
completed. Once the relearning cycle is completed, the
value in the Next Learn cycle field displays the new date
and the time of the next battery learning cycle.
Using the ServeRAID M5000 Series Battery Assembly

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Serveraid m5015Serveraid m5014 sasServeraid m5014 sataServeraid m5015 sasServeraid m5015 sata

Table of Contents