Page 3
Index Date Name Issue 2013-04-03 A. Heller Original 2014-11-07 Chr. Fechteler 14 / 608 2015-11-12 Chr. Fechteler 15 / 609 2015-12-04 Chr. Fechteler 15 / 651 Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 2 -...
Page 4
Any passing on, duplication and/or transfer by means of electronic or mechanical means, also extracts thereof, of this operating manual, requires express prior written permission. Copyright Wärtsilä JOVYATLAS EUROATLAS GmbH. All rights reserved. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 3 -...
OFFLINE MODE FREE RUNNING MODE 7.7.1 FREE RUNNING ON 7.7.2 FREE RUNNING OFF BYPASS TOLERANCE / BYPASS-ACTIVATION/DEACTIVATION 7.8.1 FREE RUNNING ON, BYPASS DEACTIVATED 7.8.2 FREE RUNNING ON, BYPASS ACTIVATED Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 4 -...
Page 6
DESCRIPTION OF THE RELAY CARD POWERPACK S 1002 13.1 EXTENDED BACKUP TIMES 13.2 BATTERY OPERATION 13.3 SERVICE LIFE OF BATTERIES 13.4 INSTRUCTIONS FOR USING THE BATTERIES REPLACING AN INTERNAL UPS BATTERY NOTES Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 5 -...
The installed battery is constantly being charged up by means of a charging rectifier with a charge preservation charging stage which is gentle on the batteries. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 6 -...
The output of the UPS unit also carries a voltage in the case of a power failure! This is why the installation engineer must mark the outputs and power sockets on the UPS unit clearly according to EN 62040. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 7 -...
Page 9
An operating fault can lead to total loss of power supply to the attached power consumer loads! A power failure for a switched in manual bypass will lead to crashing of the power consumer loads! Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 8 -...
10 kg Weight of UPS UPS incl. 1 Batteryunit about 22.5 kg incl. battery UPS unit WÄRTSILÄ JOVYTEC PMS 2002K Battery rack POWERPACK S 1002 (according to backup time: 1-2) Scope of delivery Hardware/software Manual BAX 4837E Interface cable Software UPSMON (No support) Wärtsilä...
Page 11
UPS unit WÄRTSILÄ JOVYTEC PMS 3002K Battery rack POWERPACK S 1002 (according to backup time: 1-3) Scope of delivery Hardware/software Manual BAX 4837E Interface cable Software UPSMON (No support) Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 10 -...
Page 12
UPS unit WÄRTSILÄ JOVYTEC PMS 3002K Battery rack POWERPACK S 1002 (according to backup time: 1-3) Scope of delivery Hardware/software Manual BAX 4837E Interface cable Software UPSMON (No support) Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 11 -...
LED – UPS fault, lights red in case of an internal fault FUNC key for selecting the parameters ENTER key for querying set parameters ON/OFF button for switching the UPS unit on and off Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 13 -...
Powerpack Front and Rear View Picture 10: Front view Picture 11: Rear view Position Designation Connecting jack for an optional additional battery pack Battery cable for UPS Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 15 -...
Installation For installation the two supplied angles are to be mounted on both sides as shown on the sketch Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 16 -...
Attach the critical loads by means of the output sockets. Connect up the battery pack supplied by means of the the battery connection. All connecting up work is now complete. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 17 -...
“UPS OFF“. The UPS unit is now shut-down. Please note: The internal fans of the UPS will continue to run as long as the input voltage is applied. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 18 -...
Press any key in the function panel and the alarm will be switched off. The cause of the alarm is shown in the display. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 19 -...
TEMPERATURE = 28°C Temperature of the UPS BAT PACK NUM = 2 Number of battery packs used RATING = 2000VA Nominal value of the UPS in VA CPU VERSION 3.12 CPU software Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 20 -...
The manual bypass function should always be switched off since for a switched on manual bypass the load in the case of a power failure cannot be supplied by the UPS. The UPS should we switched off and then switched on again before the generator is switched. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 21 -...
49Hz, for example 48Hz, then the input frequency is outside the specified values for the narrow input frequency range and the UPS unit switches to battery operation and supplies the load via the inverter with 50Hz. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 22 -...
Free running mode On, bypass activated A fault occurs CPU on UPS checks whether the narrow input frequency window (±2%) and voltage window is being maintained if parameter OK. Switch-over to bypass since bypass is activated. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 23 -...
Synchronisation failed New start (line abnormal) per second Switch off UPS using the ON/OFF button Battery fault 3 x bleep No battery or a faulty one Connect up a battery. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 24 -...
Input Output AC fault on output Output Discharge battery Output +8/-24 VDC Figure 5: RS232 interface P L E A S E N O T E! Maximum value 24VDC/50mA! Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 25 -...
STOP function was activated. Figure 6: Electronic STOP Manual bypass (optional) For these UPS – Devices an optional External Manual Bypass is available. Please refer to manual BAX 3945 for further explanations! Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 26 -...
7 – 5 opened closed Free Power failure Output 9 – 5 opened closed When using the contacts with the inverted logic the contact positions are set vice versa! Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 27 -...
Extended backup times The UPS unit needs two or more battery racks to achieve longer backup times. The WÄRTSILÄ JOVYTEC PMS 2002k / S 3002k allows one to connect up to two or three battery packs in parallel. P L E A S E N O T E Before plugging in the battery plug, the voltage at the battery jack on the UPS unit and the battery used must be checked to ensure that they both have the same voltage and polarity.
Please observe in this chapter guidelines from the manufacturer for your type of battery. Data sheets for battery instruction manuals for the batteries in your UPS unit can be found on http://www.jovyatlas.com/ja/POWERMASTER-S1001-S3002,120-6-2 Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E - 30 -...
Note: Not only a single block but the complete battery should be replaced in once to ensure a proper matching of all blocks. Echanging of single blocks shall be preformed only by skilled personnel. Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E...