WÄRTSILÄ JOVYTEC POWERMASTER PMS 6000 Operating Manual
WÄRTSILÄ JOVYTEC POWERMASTER PMS 6000 Operating Manual

WÄRTSILÄ JOVYTEC POWERMASTER PMS 6000 Operating Manual

Table of Contents

Advertisement

Quick Links

WÄRTSILÄ JOVYTEC POWERMASTER PMS 6000 Operating Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the JOVYTEC POWERMASTER PMS 6000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for WÄRTSILÄ JOVYTEC POWERMASTER PMS 6000

  • Page 1 _________ l � -' -------- - - ИБП Jovyatlas Jovytec PMS 6000 - руководство по эксплуатации. Юниджет Постоянная ссылка на страницу: https://www.uni-jet.com/catalog/istochniki- besperebojnogo-pitaniya/on-line-ibp-1-kva-10kva/jovytec-pms-6000.html...
  • Page 2 Operating Manual Wärtsilä JOVYTEC PMS 6000 BAX 2935 E...
  • Page 3 Index Date Name Revision 08.04.2009 Technik Original 2015-07-22 Chr. Fechteler 15/381 Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 2 -...
  • Page 4 N O T E S ! Notes concerning this operating manual Thank you for deciding to purchase this uninterrupted power supply unit (UPS) model JOVYATLAS POWERMASTER S 6000. It represents reliable protection for the attached consumers. Please read through this manual very carefully This manual contains regulations covering safety, installation and operating methods which will help you guarantee to obtain the full performance und operational readiness which the UPS can offer.
  • Page 5: Table Of Contents

    TABLE OF CONTENTS Chapter Contents Page GENERAL NOTES DESCRIPTION OF THE SYSTEM GENERAL DESCRIPTION OF THE FUNCTION TECHNICAL DATA DIMENSIONS AND VIEWS OF THE UPS UNIT DIMENSIONS AS A 19“ VERSION DIMENSIONS AS A FLOOR-MOUNTED APPLIANCE DIMENSIONS AS A WALL-MOUNTED APPLIANCE FRONT AND REAR VIEW OF THE WÄRTSILÄ...
  • Page 6 7.7.5 FREE RUNNING ON, BYPASS ACTIVATED 7.7.6 GENERATOR MODE ERROR MESSAGES AND THEIR REMOVAL 7.8.1 OPTICAL AND ACOUSTICAL ERROR MESSAGES SERVICE INFORMATION REMOTE MONITORING CONNECTING THE UPS TO THE COMPUTER ASSIGNMENT OF THE RS232 INTERFACE USB PORT (OPTIONAL) SPECIAL EQUIPMENT 10.1 ELECTRONIC STOP FUNCTION 10.2...
  • Page 7: General Notes

    General notes N O T E! The UPS should be attached to the mains supply and switched on at the latest 4 weeks after receipt in order to prevent the battery discharging itself. P L E A S E N O T E! The batteries used are just designed for the required backup time to meet the nominal load of the UPS.
  • Page 8: General Description Of The Function

    General description of the function Normal operation During normal operation the battery and the inverter are supplied with power via a rectifier (online operation). The change-over from alternating voltage to direct voltage and back to alternating voltage again is achieved by a sinusoid output voltage with a low distortion factor.
  • Page 9 Fault in the inverter or an overload (bypass operation) In the case of a fault occurring in the inverter or an overload, a switch-over device switches the load back to the mains. This means that, in the case of a power failure, the connected consumers will no longer be supplied with power.
  • Page 10: Technical Data

    Technical data JOVYATLAS POWERMASTER S 6000 Output 6000VA / 4200W cos  0,7 ind. 230V Input voltage ranges Voltage 168V - 276V (0-100% load) 140 - 159V (0-70% load) 120 - 139V (0-40% load) Network supply Current Frequency 50Hz ±3Hz or 60Hz ±3Hz Phase Single phase Power factor...
  • Page 11: Dimensions And Views Of The Ups Unit

    Dimensions and views of the UPS unit Dimensions as a 19“ version Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 10 -...
  • Page 12: Dimensions As A Floor-Mounted Appliance

    Dimensions as a floor-mounted appliance Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 11 -...
  • Page 13: Dimensions As A Wall-Mounted Appliance

    Dimensions as a wall-mounted appliance Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 12 -...
  • Page 14: Front And Rear View Of The Wärtsilä Jovytec Pms 6000

    Front and rear view of the WÄRTSILÄ JOVYTEC PMS 6000 ON/OFF FUNC STATUS ON-LINE ON-BAT BYPASS FAULT ENTER ESCAPE Graphic 7: Front View POWERMASTER S 6000 4. 5. Graphic 8: Rear View POWERMASTER S 6000 11. 12. 13. 14. 15. Position Designation Ventilation Inlet...
  • Page 15: Front And Rear View Of The Jovyatlas Powerpack S 6000

    Front and rear view of the JOVYATLAS POWERPACK S 6000 Graphic 9: Front View POWERPACK S 6000 Graphic 10: Rear View POWERPACK S 6000 Position Designation Cover Plate, left and right (dismantleable) Mounting- and Retaining Bracket for 19“ mounting (dismantleable) Battery Lead USV Battery Jack (for further Battery Packs) Wärtsilä...
  • Page 16: Installationsoptions For Jovyatlas Powermaster S 6000

    Installationsoptions for JOVYATLAS POWERMASTER S 6000 5.6.1 Powermaster S 6000 for verticale - or for wall mounting: Upright ground mounting Upright wall mounting Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 15 -...
  • Page 17: Powermaster S 6000 Mounted In 19" Cabinet

    5.6.2 Powermaster S 6000 mounted in 19“ Cabinet: Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 16 -...
  • Page 18: Powermaster S 6000 As Table Device

    5.6.3 Powermaster S 6000 as Table Device: Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 17 -...
  • Page 19: Electrical Connection

    Electrical connection P L E A S E N O T E Only trained personnel are allowed to work on the UPS unit. Observe all correponding safety regulations. Marking of cables is to be according to DIN EN 60445! When connecting to the UPS unit, ensure use of an adequately sized protective- conductor connection! P L E A S E N O T E When working on the batteries it is possible for dangerous situations to arise...
  • Page 20: Electrical Connection Of Ups For One Mains Feeding

    Electrical connection of UPS for one mains feeding Switch off the input- and output switch on rear side of the UPS Dismantle the cover plate with a Phillips Screw Driver Guide the leads through the foreseen cut outs Connect the input cable to the terminals with the designation input L1, N, PE Make sure that there is a wire connection between the terminals J and L at the terminal rail bypass.
  • Page 21: Electrical Connection Of Ups For Two Mains Feeding

    Electrical connection of UPS for two mains feeding P L E A S E N O T E Both mains feeding must have the same connection. Don´t exchange L1, N , PE, this will cause a short circuit which will destroy the UPS!! 1.
  • Page 22: Commissioning The Ups Unit

    Commissioning the UPS unit P L E A S E N OT E! The unit should be started over the input mains. If the input mains is not available for a short time then it is also possible to start the unit over the external battery. It is a basic prerequisite for this operating mode that the UPS unit was one time operated over the energy supplier’s mains network.
  • Page 23: Shutting-Down The Ups Unit

    Shutting-down the UPS unit When shutting down the unit please proceed as follows: Switch off all consumers Press the “ON/OFF” button in the front panel for 5 seconds. An acoustic sound (bleep) is emitted while pressing the “ON/OFF” button and the message: Switching off soon appears in the display, and then the message “UPS OFF“.
  • Page 24: Operating And Indicating Elements

    Operating and indicating elements ON/OFF FUNC STATUS ON-LINE ON-BAT BYPASS FAULT ENTER ESCAPE Graphic 15: Display Function of LED´s and function keys Display indicator The display indicator informs about the operating modes, menu points and parameters. ON/OFF button The UPS unit can be switched on and off using the ON/OFF button. The formalism is as follows: The UPS unit is switched on by pressing the ON/OFF button for about 3 seconds.
  • Page 25: Parameters Of The Ups Unit

    6. ESCAPE button By pushing the ESCAPE button you can leave the menue. The operating mode and actual condition of the UPS is displayed by means of 5 LED´s on the operating panel. The conditions are as follows: 7. ON : This LED glows green if the UPS is switched on 8.
  • Page 26: Configuration Of The Ups Unit

    Configuration of the UPS unit Use of the function display and the function keys allows diverse settings to be made on the UPS unit. The formalism is as follows: In order to achieve Configuration Mode it is necessary to press the FUNC button for 2 seconds. The first configuration parameter appears in the display.
  • Page 27: Manual Testing Of The Ups

    Manual testing of the UPS The UPS unit is capable of conducting a self-test. Pressing the , FUNC button causes the unit to run with its configurations menu. Manoeuvre to the point: Manual Battery Test. Now press the ENTER button. The message TEST? appears in the display.
  • Page 28: Setting The Bypass Tolerance + Activation/Deactivation Of The Bypass

    7.7.3 Setting the bypass tolerance + activation/deactivation of the bypass The UPS unit offers the option of activating and deactivating the bypass. There is also the option of setting the bypass network tolerance via the display (see Chapter 7.4). The functionality of the bypass tolerance is described below. If the UPS unit has a fault and the bypass is activated but the input voltage does not have the quality to supply the consumers then the following examples can arise: 7.7.4...
  • Page 29: Generator Mode

    7.7.6 Generator mode Generator mode (adjustable via the panel) ensures that the UPS unit is not constantly switching over to battery operation, since the output voltage of the generator often demonstrates distortions or irruptions, but remains in online mode and thus a sinusoidal output voltage for the consumers is achieved. This functionality has a low loading effect on the battery which means that the working life of the battery is maintained.
  • Page 30: Service Information

    Service information S E R V I C E – H O T L I N E ! Tel: +49 4958 - 9394 - 30 Fax: +49 4958 - 9394 - 10 E-mail: service@jovyatlas.de Internet: http://www.jovyatlas.de ATTENTION ! All kind of maintenance and/or servicing may be carried out by authorized personnel only.
  • Page 31: Assignment Of The Rs232 Interface

    Assignment of the RS232 interface The RS 232 interface uses a 9-pin SUB-D connector (jack). Assignment of the SUB-D connector is as described in the table below. Pin assignment for the RS 232 interface RS 232 interface (Rear side of UPS) SIGNAL DIRECTION FUNCTION...
  • Page 32: Ups Internal Manual Bypass ( Service - Bypass)

    10.2 UPS internal manual bypass ( Service – Bypass) On the rear side of the ups is also an internal manual bypass available. This internal manual bypass is protected by a cover plate, because switching without forcing the ups to bypass mode will destroy the ups. For using this internal manual bypass, the coverplate has to be removed.
  • Page 33: Volt-Free Messages Via The Relay Card (Optional)

    Volt-free messages via the relay card (optional) 11.1 Description of the relay card There is also the option to fit the UPS unit with a relay card (optional). This relay card provides voltage-free contacts for external further use. These contacts are designed a standard as closing contacts, that is they close in the case of a fault.
  • Page 34 Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 33 -...
  • Page 35: Powerpack S 6000

    POWERPACK S 6000 12.1 Extended backup time The UPS unit needs two or more battery racks to achieve longer bridging times. The JOVYATLAS POWERMASTER S 6000 permits to use up to five battery packs in parallel, which results in the following backup times: Number of Total weight of Total weight of...
  • Page 36: Service Life Of Batteries

    12.3 Service life of batteries Use of closed lead batteries at temperatures above 20°C reduces the expected working life. The table from Eurobatt gives some indication of the approximate working life of the batteries used. Nominal working life of batteries 10 - 12 years 6 - 9 years 3 - 5 years...
  • Page 37: Replacing An Internal Ups Battery

    Replacing an internal UPS battery UPS units of the type JOVYATLAS POWERMASTER S 6000 offer the option of replacing the battery while operating. One must ensure in this case that the UPS unit is running in normal mode and not in autonomy mode.
  • Page 38: Notes

    Notes ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ Wärtsilä JOVYTEC PMS 6000 BAX 2935_en - 37 -...

Table of Contents