F&F LE-03MP Manual page 10

Electric energy meter, 3-phase
Table of Contents

Advertisement

address
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
* Automatic operation is the mode with two active functions: automatic
relay disconnection if the set overcurrent threshold is exceeded and swit-
ching on the prepaid mode.
Register parameters
description
Meter address: range 1÷255
L1 voltage [V] (×0.01)
L2 voltage [V] (×0.01)
L3 voltage [V] (×0.01)
L1 current intensity [A] (×0.01)
L2 current intensity [A] (×0.01)
L3 current intensity [A] (×0.01)
L1 active power [kW] (×0.001)
L2 active power [kW] (×0.001)
L3 active power [kW] (×0.001)
L1+L2+L3 active power [kW] (×0.001)
Protection current [A] (×0.01)
Automatic operation mode
(0:OFF/1:ON)*
Current state of relay (0:OFF/1:ON)
Manual relay control (0:OFF/1:ON)
Frequency [Hz] (×0.01)
- 10 -
type
atr
int
R/W
int
R
int
R
int
R
int
R
int
R
int
R
int
R
int
R
int
R
int
R
int
R/W
int
R/W
int
R
int
R/W
int
R