Wiring; Activation Switch; Cable Types And Lengths; Grounding Of Protective Shields - ABB ACS880-11 Hardware Manual

Hide thumbs Also See for ACS880-11:
Table of Contents

Advertisement

Wiring

For the electrical specifications of the STO connection, see the technical data of the
control unit.

Activation switch

In the wiring diagrams, the activation switch has the designation [K]. This represents a
component such as a manually operated switch, an emergency stop push button switch,
or the contacts of a safety relay or safety PLC.
• In case a manually operated activation switch is used, the switch must be of a type
that can be locked out to the open position.
• The contacts of the switch or relay must open/close within 200 ms of each other.
• An FSO-xx safety functions module or an FPTC-0x thermistor protection module
can also be used. For more information, see the module documentation.

Cable types and lengths

• Double-shielded twisted-pair cable is recommended.
• Maximum cable lengths:
• 300 m (1000 ft) between activation switch [K] and drive control unit
• 60 m (200 ft) between multiple drives
• 60 m (200 ft) between external power supply and first control unit
Note: A short-circuit in the wiring between the switch and an STO terminal causes a
dangerous fault. Therefore, it is recommended to use a safety relay (including wiring
diagnostics) or a wiring method (shield grounding, channel separation) which reduces
or eliminates the risk caused by the short-circuit.
Note: The voltage at the STO input terminals of the control unit must be at least 17 V DC
to be interpreted as "1".
The pulse tolerance of the input channels is 1 ms.

Grounding of protective shields

• Ground the shield in the cabling between the activation switch and the control unit
at the control unit only.
• Ground the shield in the cabling between two control units at one control unit only.
The Safe torque off function 211