Derating For Output Voltage Boost; Fuses (Iec) - ABB ACS880-11 Hardware Manual

Hide thumbs Also See for ACS880-11:
Table of Contents

Advertisement

170 Technical data
Output ratings with selection High speed mode of parameter 95.15 Spe-
Maximum output
ACS880-11-
07A6-5
11A0-5
014A-5
021A-5
027A-5
034A-5
040A-5
052A-5
065A-5
077A-5
101A-5
124A-5
156A-5
180A-5
U n
Nominal voltage of the drive
f max
Maximum output frequency with High speed mode
I n
Continuous rms output current. No overload capability at 40 °C (104 °F).
I Ld
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I Hd
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes

Derating for output voltage boost

See ACS880-11, ACS880-31, ACS880-14, ACS880-34, ACS880-17, ACS880-37 drives
product note on DC voltage boost

Fuses (IEC)

Fuses protect the input cable in short-circuit situations. They also restrict drive damage
and prevent damage to adjoining equipment in case of a short-circuit inside the drive.
ABB recommends the high speed aR fuses specified below. The gG fuses can be used
for frames R3 and R6 if they operate rapidly enough (max. 0.1 seconds). The operating
time depends on the supply network impedance and the cross-sectional area and length
of the supply cable. Obey the local regulations.
Nominal use
frequency
f max
Hz
500
500
500
500
500
500
500
500
500
500
500
500
500
500
(3AXD50000691838
cial HW settings
Light-duty use
I N
I Ld
A
6.5
6.2
9.4
8.9
12.0
11.4
18.0
17.1
23.0
21.9
29
29
37
39
46
101
124
118
144
136
169
160
[English]).
Heavy-duty use
I Hd
A
A
4.4
6.5
9.4
12.0
18.0
28
23
28
23
35
29
37
33
44
39
91
77
96
87
147

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents