5.13. DISPLAY AND CANCELLATION OF ALARMS AND WARNINGS

The system notifies the user about the system failures by warnings that are canceled automatically and by alarms that have to be canceled man-
ually. The latter are recommended to be canceled by a specialist prior to finding out the causes of the alarm. Information on alarms and warnings
is also displayed in the main window ADJUSTER › VENTILATION CONTROL. If at least one alarm is active, the system is shut down and external failure
indication is activated. Alarms and warnings can be reviewed and canceled in the window ADJUSTER › ALARMS or USER › ALERT. All possible alarms
and warnings are provided in the table below.
INDICATION
ALARMS LIST
Warning! Rotor broken belt alarm
.
Alarm! Fireplace protection activated
A.2
Warning! Dryness protection activated
.3
Warning! Plate heat exchanger frost protection
.
activated
Alarm! Plate heat exchanger frost protection system
A.5
stopped
Warning! Plate heat exchanger frost protection (pres-
.6
sure relay)
Alarm! Hydronic heater frost protection. System
A.7
stopped
Warning! Too low supply temperature
.
Warning! Too high supply temperature
.
Alarm! Too low supply temperature. System stopped
A.
Alarm! Too high supply temperature. System stopped
A.
Warning! Change supply air filter (pressure relay)
.2
Warning! Change extract air filter (pressure relay)
.3
Warning! Change supply and extract filters (timeout)
.
Alarm! Power supply failure. Please, check F1 fuse
A.5
Warning! Supply air temperature sensor failure.
.6
Emergency run
Warning! Extract air temperature sensor failure.
.7
Emergency run
Warning! Exhaust air temperature sensor failure.
.
Emergency run
Warning! Outdoor air temperature sensor failure.
.
Emergency run
Warning! Hydronic heater water temperature sensor
.2
failure. Emergency run
Warning! Hydronic pre-heater water temperature sen-
.2
sor failure. Emergency run
Warning! Hydronic cooler water temperature sensor
.22
failure. Emergency run
Warning! Controller cabinet temperature sensor
.23
failure. Emergency run
Alarm! Supply air temperature sensor failure. System
A.2
stopped
Alarm! Extract air temperature sensor failure. System
A.25
stopped
Alarm! Exhaust air temperature sensor failure. Sys-
A.26
tem stopped
Alarm! Outdoor air temperature sensor failure. Sys-
A.27
tem stopped
Alarm! Hydronic heater water temperature sensor
A.2
failure. System stopped
Alarm! Hydronic pre-heater water temperature sensor
A.2
failure. System stopped
Alarm! Hydronic cooler water temperature sensor
A.3
failure. System stopped

5.14. EVENT LOG (HISTORY)

The system records 50 recent events (failures, alarms, fire damper testing results, etc.).
The log stores the description of events and time.
The event log may be reviewed in the window ADJUSTER › HISTORY or USER › MENU › HISTORY.
8
| EN
INDICATION
ALARMS LIST
Alarm! Controller cabinet temperature sensor fail-
A.3
ure. System stopped
Fire damper test OK
.32
Warning! Fire damper test failed
.33
Alarm! Heater manual protection. System stopped!
A.3
Warning! Heater automatic protection
.35
Alarm! Pre-heater manual protection. System
A.36
stopped!
Warning! Pre-heater automatic protection
.37
Alarm! Supply fan failure
A.3
Alarm! Extract fan failure
A.3
Warning! DX cooler failure
.
Alarm! Fire
A.
Alarm! Supply fan pressure protection. System
A.2
stopped
Alarm! Extract fan pressure protection. System
A.3
stopped.
Alarm! Internal system error.
A.
Alarm! Heater manual protection. Boosting.
A.5
Alarm! Pre-heater manual protection. Boosting.
A.6
Alarm! Internal communication error
A.7
Warning! DX cooler defrosting
.
Warning! Too high 3 days extract humidity. Increas-
.
ing air flow.
Warning! Too high extract humidity. Boosting.
.5
Alarm! Rotor broken belt alarm. System stopped.
A.5
Warning! Gas heater failure
.52
Warning! Gas pre-heater failure
.53
Warning! Too high condensation level
.5
Warning! Supply fan failure. Emergency run
.55
Warning! Extract fan failure. Emergency run
.56
Warning! Too low supply air flow for DX cooler
.57
Alarm! Bypass damper failure. System stopped.
A.5
Alarm! Hydronic heater/pre-heater circ. pump
A.5
failute. System stopped.
Warning! Hydronic heater/pre-heater circ. pump
W.6
failute.
MCB_miniMCB v2019.1