3.12
Linkage Control
Linking the Fire Control with
Cabinet Electronic Clasp Lock Open
1. Log in to the ECC800 WebUI as an
administrator.
2. Choose System Settings > Linkage
Control.
3. Ensure that Enable linkage control
function is set to Yes.
4. On the Linkage Group tab page, set Link
fire control with Cabinet Electronic
Clasp lock open to on.
5. Modify the AI/DI_2 signal name.
6. Enable the AI/DI device.
(Optional) NetEco Management
3.13
Data Center Management
1. Connect the communication cable.
2. Set NetEco parameters.
3. Obtain the NetEco software license.
4. Power on the server.
5. Log in to the NetEco client.
6. Load the NetEco software license.
7. Install the NE mediation.
8. Add a smart module.
9. Create an ECC800 on the NetEco.
For details, see
FusionModule500 Smart Mini Data Center V100R021C10 User Manual
Linking the Smoke Alarm with
Cabinet Electronic Clasp Lock Open
1. Log in to the ECC800 WebUI as an
administrator.
2. Choose System Settings > Linkage
Control.
3. Ensure that Enable linkage control
function is set to Yes.
4. On the Linkage Group tab page, set
Link smoke alarm with Cabinet
Electronic Clasp lock open to on.
5. Modify the AI/DI_1 signal name.
6. Enable the AI/DI device.