2. Use the Service Expert app to authenticate the startup password.
a) Download and install the Service Expert app from Huawei AppGallery.
If Huawei AppGallery has been installed on the PAD, log in to the Huawei AppGallery
client, search for Service Expert, and tap Install.
If Huawei AppGallery is not installed on the PAD, log in to Huawei AppGallery
(https://appgallery.huawei.com/), search for Service Expert, and tap Install.
b) Hold down the SW button on the ECC800 for less than 3s to enable the WiFi function.
c) Use the Service Expert app to authenticate the startup password.
Setting the Date and Time
3.4
1. Choose System Settings > System Parameters > Time.
2. Set the time zone, date, and time based on site requirements or click Obtain
Local Time, and click Submit.
Creating a Smart Module Plan View
3.5
1. Choose Home > Plan View, click Create Micro-Module in Micro-Module View, and set the
layout and device quantity based on the actual smart module scenario.
2. Drag the icons of registered devices and devices on the cabinet list to appropriate positions
in the layout to create a smart module plan view.
Adding a Southbound Device
3.6
1. Choose System Settings > Device Management > Add Device.
2. After you add a device based on the site requirements or click Auto Discover Device, the
details about the device connected to the smart module are displayed.
Commissioning a Smoke Detector
3.7
1. Set smoke detector parameters.
a)
Log in to the ECC800 WebUI as an administrator.
b)
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
c)
Set Device type to ECC800 and Device name to ECC800, and click OK.
d)
On the query result tab page, set the new signal name of AI/DI_1 to Smoke and click
Submit.
e)
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1 Port
Settings.
f)
Set Smoke sensor to Enable and click Submit.
g)
Confirm that Smoke sensor type is automatically identified as Smoke sensor.
2. Check the monitoring functions of smoke sensor.
Check Method
Simulate a smoky
environment under
the smoke detector.
Normal Connection Status
Smoke DI alarm is displayed
on the active alarm page of
the app or WebUI.
21
Alarm Clearance Method
Disconnect the smoke detector
cable and reconnect it to clear
the alarm.