Overview
1
Item
Cabinet dimensions (H x
W x D)
Installation scenario
Installation space
Power distribution
Operating temperature
Operating humidity
IP rating
Installation mode
Altitude
Cabinet Internal Layout (02116410)
Converged Cabinet: 2000 mm x 600 mm x 1100 mm
Single-cabinet scenario
The cabinet provides 42 U available space. The mounting bars are
adjustable forward or backward, and space is reserved at the rear of
the cabinet for installing PDU2000s horizontally and vertically.
6 kVA UPS
PDU2000: can be installed horizontally or vertically. IEC and GB
models are optional for horizontal installation.
Lithium battery: 100 Ah/48 V DC
Indoor: 0 ° C to +40 ° C
5%–95% RH
IP20
Installed on a concrete floor or an ESD floor
≤ 1000 m (derated when the altitude ranges from 1000 m to 4000 m)
Specifications
No.
Component
(1)
ECC800
(2)
Door status sensor
Power distribution
(3)
subrack
(4)
(5)
Lithium battery
(6)
Water sensor
(7)
Smoke detector
Temperature and
(8)
humidity (T/H)
(9)
PDU2000
2
Copyright © Huawei Technologies Co., Ltd. 2021.
All rights reserved.
Onsite
Installation
Not
required
Not
required
Not
required
Not
UPS
required
Required
Required
Not
required
Required
sensor
Required