Download Print this page

Huawei FusionModule500 Quick Manual page 23

Smart mini data center
Hide thumbs Also See for FusionModule500:

Advertisement

3. Check the T/H sensor functions.
Check Method
Check the running
information about the T/H
sensor on the WebUI.
Set T/H sensor alarm
thresholds.
Commissioning Cabinet Electronic Clasp Locks
3.10
1. Set device addresses for cabinet electronic clasp locks.
A cabinet electronic clasp lock is installed at the front and rear doors of the cabinet
respectively. The address for the cabinet electronic clasp lock on the front door is an odd
number, and that for the cabinet electronic clasp lock on the rear door is an even number.
Set a device address for a cabinet electronic clasp lock by operating the DIP switch on the
cabinet electronic clasp lock. Toggle switches 1 to 6 specify the device address in binary
mode. ON indicates 1, and OFF indicates 0.
Toggle
Address
Switch 1
1
ON
2
OFF
2. Add cabinet electronic clasp locks.
a. Log in to the ECC800 WebUI as an administrator.
b. Create a cabinet view in Smart Module View on the home page.
c. Add cabinet electronic clasp locks.
Event Notification
3.11
1. Choose System Settings > Event Notification.
2. Set outbox parameters.
3. Add an email address for receiving emails.
4. Add a mobile number for receiving event notifications.
5. Set the alarm notification delay time and add alarm notification parameters.
6. Click Confirm. In the re-authentication dialog box, enter Login password and click Submit.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group > T/H Sensor
> Running Info, and view the current cabinet temperature and
humidity.
Choose Monitoring > Aisle > T/H Sensor Group > T/H Sensor
> Running Parameters, and set High temperature alarm
threshold, Low temperature alarm threshold, High humidity
alarm threshold, and Low humidity alarm threshold as
required.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
23
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
n
n
Toggle
Switch 6
OFF
OFF

Advertisement